Setpoints, System setup, Trend viewer – KMC FLEXSTATTM BAC-10000 User Manual

Page 13: Setpoints system setup trend viewer, Configurable in the system menu. see

Advertising
background image

BAC-10000 Series

13

Operation Guide, Rev. J

System Setup

SYSTEM

SYSTEM ENABLE:

OCC OVRIDE (HRS): 1.0
INACTIVITY (SECS): 60
DISPLAY BLANKING: NO

AUTO

To adjust the system configuration values, such as

system enable (auto, off, heat, or cool), occupancy

override time, and display inactivity time-out:
1. Up/Down to move among entries.
2. Enter to select.
3. Up/Down to increment/decrement value.
Occupancy Override on this menu is the amount of

time (in hours) a manual change in the setpoint (via

the Up and Down buttons) will be allowed to over-

ride the scheduled setpoint. When the time is set to

0, the override state will last until the next schedule

change.

When Display Blanking is enabled (Y), the display

turns off at the same time the backlight goes off

(after reset, initial power-up, or time-out). When any

button is pressed, the display will reappear until the

time-out is reached again.
The menu/display/backlight time-out (seconds

since the last button is pushed) is set in Inactivity.
Access to the Main Menu, setpoint adjust, and

System/Occupancy/Fan override have a default

password level of User. This level can be changed for

each function to None, Operator, or Administrator

through this screen. Passwords are set in the (Ad-

vanced) Passwords menu. See

(Advanced) Security

Levels and Passwords on page 9

.

Trend Viewer

TREND VIEWER

1:

2: SPACE HUMIDITY 27
3: FAN

19

4: COOL 1

18

5: COOL 2

21

6:
7:

SPACE TEMP 34

TL #1 SPACE TEMP

APR11 1:27PM, 70.3

APR11 2:27PM, 71.3
APR11 3:27PM, 71.6
APR11 4:27PM, 71.8
APR11 5:27PM, 76.3
APR11 6:27PM, 81.2
APR11 7:27PM, 82.3

To view trend log buffers, press:
1. Up/Down to move among entries.
2. Enter to select.
Trend logs are set up in the

(Advanced) Trend Logs

menus (see

page 10

).

Setpoints

SETPOINTS

COOL SETPT:

HEAT SETPT: 67° F
COOL SETBACK: 80° F
HEAT SETBACK: 64° F
MIN SETPT DIFF: 2° F
DEADBAND: 2° F
DEHUM SETPT: 60 % RH

74° F

In the Setpoints menu, deadband, setbacks, and

setpoints for various values are set. (The room

temperature setpoint can also be manually changed

from the Home menu.)
To adjust the setpoints, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Up/Down to increment/decrement value.