BAC-10000 Series

5

Operation Guide, Rev. J

Advanced Menu

ADVANCED

APPLICATION

CB PROGRAMS
COMMUNICATION
DATE/TIME
DEVICE
INPUTS
LIMITS

The Advanced Menu displays various submenus.

Not all submenus can be seen on the screen at one

time. Scroll up or down to see additional submenus.

To select the desired submenu, press:
1. Up/Down to move.
2. Enter to select.
NOTE: The Advanced Menu has more submenus

than can appear on the screen at once. Keep

scrolling up or down to see all the options.

(Advanced) Application Options

APPLICATION

DEGREES SCALE: °F

APP:

OPT: 4-PIPE
ADDITIONAL SETUP

FAN COIL

ADDITIONAL SETUP

DAMPER

FAN
HUMIDITY
SENSORS
VALVE

To change ° F or C, preprogrammed application type,

and options, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
The type of application (as well as the model of

FlexStat) affects the context-sensitive options under

Additional Setup.

Auxiliary Heat (Heat Pump Only)

AUX HEAT SETUP

AUX HEAT:

DELAY (MINS): 60

COMP LOCKOUT

Damper Setup

DAMPER SETUP

ECON:

MIN POSITION (%): 10
CNTRL (0–100%): 2–10 V
ECON ENBLE TEMP: 55° F
LOW LIMIT ALARM: 45° F

MODULATING

NOTE: If the Economizer option is selected when

there is no mixed air temperature sensor

connected, a Low Limit Alarm will result.

See

Alarms on page 11

.

Fan Setup

FAN SETUP

SPEEDS:

OFF DELAY (SECS): 180
UNOCC: AUTO
OCC: AUTO

CONSTANT SPEED

NOTE: For a Fan Fail Alarm, see

Sensor Setup on

page 6

and

Alarms on page 11

.

Humidity Setup

HUMIDITY SETUP

DEHUMIDIFICATION

HUMIDIFICATION

DEHUMIDIFICATION

DEHUM:

ALLOW HTG DEHUM: NO
DEHUM SETPT: 60%RH
DEHUM DEADBAND: 5%RH

ENABLE

NOTE: If a dehumidification option is enabled, the

Space Humidity Alarm will also be enabled.

See

Alarms on page 11

.