Output, fan, and relay issues, Analog output does not work, Fan does not run – KMC FLEXSTATTM BAC-10000 User Manual

Page 20: Relay (internal) does not work, Caution

Advertising
background image

BAC-10000 Series

20

Operation Guide, Rev. J

Fan Does Not Run

NOTE: The animated fan icon is coupled with

BV18 in the packaged programming (not

the actual fan output terminal).

• Select Occupied mode from the Home Menu—

see

H/C, Fan, Occupancy, and Override on page 3

.

• Override the fan to On from the Home Menu—

see

H/C, Fan, Occupancy, and Override on page 3

.

See

Wiring Issues on page 21

.

• Check that the appropriate application is se-

lected—see

(Advanced) Application Options on

page 5

.

Check the fan configuration—see

Fan Setup on

page 5

.

• Restart the FlexStat. After a low limit alarm is

generated, the fan will not run until after the

FlexStat is restarted. (See

Resetting the FlexStat

on page 14

.)

Relay (Internal) Does Not Work

CAUTION

Relays are for Class-2 voltages (24 VAC) only.
Do not connect line voltage to the relays!

NOTE: Max. output current is 1 A for individual

relays @ 24 VAC/VDC or a total of 1.5 A

per bank of 3 relays (relays 1–3, 4–6, and

7–9). Do not attach a device that draws

current that exceeds the corresponding

value. Relays are NO, SPST (Form “A”).

• Check current draw of load. Substitute an output

device that draws less current.

• Check that the output is on.
See

Wiring Issues on page 21

.

• Restart the FlexStat.
• If Restore Factory has just been performed, see

the Note and Cautions in

Restore Factory on

page 15

.

Output, Fan, and Relay Issues

Analog Output Does Not Work

CAUTION

Do not mistakenly connect 24 VAC to an analog
output ground. This is not the same as a relay’s
switched common. See the backplate’s terminal
label for the correct terminal.

NOTE: The maximum current of an analog output

is 20 mA @ 12 VDC. Excessive loads will

be clamped at the maximum. Relays may

chatter or fail to latch if they need more

current than the maximum allowed. KMC

REE-3111/3112 relays, for example, could be

connected to the analog outputs, but REE-

3211/3221/3213 relays would not operate

reliably with analog outputs because their

required power exceeds the FlexStat’s

capacity. (REE-3211/3221/3213 relays could,

however, be used with the FlexStat relays

and a separate power source.)

• Check current draw of load—it must be 20 mA or

less. Substitute an output device that draws less

current.

• Check that the output is on.
• See

Wiring Issues on page 21

.

See also

Fan Does Not Run on page 20

.

• If Restore Factory has just been performed, see

the Note and Cautions in

Restore Factory on

page 15

.

• If the firmware has just been upgraded, firm-

ware for the wrong model type may have been

installed (e.g., BAC-1xx63 firmware accidentally

installed in a model BAC-1xx36). In the About

menu, ASV may simply read “CUSTOM” instead

of something like “BAC_1xx36 R1.1.0.5” as it

normally would have done. If so, repeat the firm-

ware upgrade and ensure that the correct type of

firmware is selected for the connected model.

NOTE: ASV in the About menu will also show

CUSTOM if any built-in Control Basic

program (1–5) is not running or has auto-

run disabled.