BAC-10000 Series

6

Operation Guide, Rev. J

Sensor Setup

SENSOR SETUP

IN 2:

DISCH AIR TEMP

The Input 2 sensor (AI2) can be configured for

discharge air temperature (Type III thermistor is the

default), fan status (dry contact), or unused.
• If set for discharge air temperature, the sensor

can be calibrated and changed from the default

Type III thermistor to a Type II. See

(Advanced)

Inputs on page 8

.

• If set for discharge air temperature, Trend Log

#2 is automatically created and monitors the

discharge air temperature, but it has no effect on

operation.

• If set for fan status and no closed contact is

detected when there is a call for fan operation, a

Fan Fail Alarm is created. See

Alarms on page 11

.

• If set for unused, built-in applications will not

use AI2, but the input would be available to

custom programming.

Staging Setup

STAGING

STG DELAY (MINS):

3

Valve Setup

VALVE SETUP

TYPE:

ACTION: NRM OPEN

2–POSITION

(Advanced) CB (Control Basic) Programs

CB PROGRAMS

PROG1:

PROG2: RUNNING
PROG3: RUNNING
PROG4: RUNNING
PROG5: RUNNING
PROG6: HALTED
PROG7: IDLE

RUNNING

PROGRAM #1

SETPOINTS & MODES
AUTO-RUN: TRUE
CHANGE: READY
STATE: RUNNING
HALT REASON: NORMAL
HALT DESC:
OUT OF SERVICE: FALSE

To halt or load/run the built-in (1–5) and custom

(6–10) Control Basic programs, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Left to move among value fields.
4. Up/Down to increment/decrement value.
NOTE: If custom Control Basic programs are

installed and a restore to factory settings

is performed, all factory programs are

restarted but all custom Control Basic

programs are halted. Change the state

of each program by loading/running the

program from the CB Programs menu (or

BACstage).

NOTE: If custom Control Basic programs are

installed and set to autorun, whenever the

firmware is updated, ALL (factory and

custom) programs are halted.

If custom Control Basic programs are

installed but NOT set to autorun,

whenever the firmware is updated, factory

programs are restarted but any (manual)

running custom programs are halted at

restart.

Change the state of each custom program

by using the Update Manager or loading/

running each program from the CB

Programs menu (or BACstage).

UPDATE MANAGER

PROGRAM CONFIG ERROR

ENABLE FACTORY:

ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE

NO

NOTE: Customized programs are the responsibility

of the user. KMC Controls does not provide

support for such programs.