(Advanced) Security Levels and Passwords

SECURITY

ACCESS LEVELS

PASSWORDS

ACCESS LEVELS

SETPOINT ADJ:

MAIN MENU: ADMIN
SYSTEM MODE: OPER
OCC OVERRIDE: USER
FAN OCC/UNOCC: OPER

NONE

PASSWORDS

USER:

OPERATOR:
ADMIN:

1 0 0 0
1 2 3 4
5 6 7 8

Access to the Main Menu, Setpoint Adjust, and

System/Occupancy/Fan settings have a default

password level of User. This level can be changed for

each function to None, Operator, or Administrator

through the Access Levels menu. Passwords are set

in the Passwords menu.
Any person can view the display but might not be

able to change any settings without logging in with

one of the three levels of passwords:
• None (Level “0”): No password is required

(everyone has access).

• User (Level 1): See the Menu Items Access Levels

chart.

• Operator (Level 2): See the Menu Items Access

Levels chart.

• Administrator (Level 3): Can access all menus

and change all editable values. DO NOT

FORGET THIS PASSWORD!

NOTE: Setting a password to (the default) 0000

eliminates the password prompt and

allows full access for that level. If no

password is set for ADMIN, no password

prompt will occur. If any password is set

for ADMIN, the menu items accessible

at the various levels are shown in the

following chart.

NOTE: Changes in security levels and/or

passwords take effect when the current

Administrator log-in has timed out. Log-

ins last until 60 seconds (default) after

the last button press. Desired length of

inactivity time-out can be changed in the

Systems submenu.

NOTE: When setting a password, the Up button

increases the alphanumeric value (0

through 9 and then A through Z). The

Down button decreases the value. DO NOT

FORGET THE ADMIN PASSWORD!

To enter an alphanumeric password at the prompt:
1. Up/Down to move.
2. Enter to select.
3. Up/Down to increment/decrement value.
The required password level is specified in the

prompt.
For additional security and protection from

vandalism, install the FlexStat inside a third-party

locking thermostat guard/cover (but proper airflow

must be maintained).

Menu Items Access Levels

Menus

User Operator Administrator

Home Screen

* = Selectable, Default is User

Setpoint Adjust (Up/Down)

x*

x*

x*

System Mode (Auto/Heat/Cool/Off)

x*

x*

x*

Occupancy Override (On/Off)

x*

x*

x*

Fan Modes (Auto/On/Off)

x*

x*

x*

Main Menu* (Default is User)

About

x

x

x

Advanced

x

x

Alarm

x

x

Date/Time

x

x

Schedule

x

x

Setpoints

x

x

System

x

x

Trend Viewer

x

x

x

Advanced Menu

Application

x

Additional Setup

x

Control Basic Programs

x

x

Communication

x

Date/Time

x

x

Device

x

Inputs

x

x

Limits

x

x

Motion Sensor

x

x

Security

x

Trend Logs

x

x

Test

x

x

This chart shows conditions in which an administrator password is set