Troubleshooting, Alarm issues, Alarm, (false) fan fail – KMC FLEXSTATTM BAC-10000 User Manual

Page 17: Alarm, (false) low limit (freeze stat), Alarm, (false) space temp. or humidity, Communication issues, Firmware upgrade fails, Kmd-5576 communication faulty, Ms/tp network communication faulty

Advertising
background image

BAC-10000 Series

17

Operation Guide, Rev. J

Troubleshooting

Alarm Issues

Alarm, (False) Fan Fail

• Check configuration. Be sure the Fan Status

option is not selected when there is no sensor/

switch for it.

• Check that the IN2 (fan status) input pull-up

resistor switches are fully latched in the correct

positions. Any passive, dry contact should use

the 10K Ohm setting. (See the Connections and

Wiring section of the relevant BAC-10000 Series

Installation Guide.)

• Check IN2 (fan status) input wiring.
• Check the connected fan status sensor/switch.
• Using BACstage or TotalControl, check that AI2

(fan status) is not configured as “Out Of Service.”

Alarm, (False) Low Limit (Freeze Stat)

• Check the Low Limit Alarm setting—see

Damper

Setup on page 5

.

• Check configuration. Be sure the Economizer

option is not selected when there is no mixed air

temperature sensor.

• Check that the IN3 (mixed air temp.) input

pull-up resistor switches are fully latched in the

correct positions (see the Connections and Wiring

section of the relevant BAC-10000 Series Installa-

tion Guide).

• Check IN3 (mixed air temperature) input wiring.
• Check the connected mixed air temperature sensor.
• Using BACstage or TotalControl, check that AI3

(mixed air temp.) is not configured as “Out Of

Service.”

NOTE: After a low limit alarm is generated, the

fan will not run until after the FlexStat

is restarted. See

Resetting the FlexStat on

page 14

.)

Alarm, (False) Space Temp. or Humidity

• See

Alarms on page 11

.

• See

Temperature Reading Is Incorrect on page 19

.

• See

Temperature Setpoint Is Not Maintained on

page 19

.

• Using TotalControl, adjust the limits or time

delay.

Communication Issues

Firmware Upgrade Fails

• Ensure the WD (watch dog) jumper is temporar-

ily removed during the upgrade process (see the

KMD-5699 Installation Guide, P/N 913-019-04).

Reinstall the pin on the left and center pins after

the upgrade process is complete.

• Check connections.
• Ensure firmware for the correct model is selected

in the Firmware Upgrade Tool.

NOTE: If firmware for a wrong model is acciden-

tally installed, the outputs will not match the

applications/configuration on the display.

NOTE: Backing up the existing settings and

firmware image before or during the

upgrade process is good practice.

NOTE: Restoring to the factory defaults and

reconfiguring might be needed if how the

FlexStat operates changes. Read all notes

accompanying the firmware update!

KMD-5576 Communication Faulty

• Upgrade to the latest version of BACstage (ver.

2.4.0.25 or later required).

• Check the settings for the USB port on the

computer (Device Manager > Ports) and the

MS/TP port in BACstage (Access > Connection

Parameters).

• Reduce the Max Master number down to the

minimum needed for that network—see

(Ad-

vanced) BACnet Communications on page 7

.

• Install latest driver and check latency settings.

See Latency Settings for KMD-5576 Service Bul-

letin (SB0308A) on the KMC web site.

• See also

MS/TP Network Communication Faulty

below.

MS/TP Network Communication Faulty

• Reduce the Max Master number down to the

minimum needed for that network—see

(Ad-

vanced) BACnet Communications on page 7

.

• Check that EOL switches are fully latched in the

correct positions (see the relevant BAC-10000

Series Installation Guide).

• Check MAC address and device instance num-

bers.

• Check baud rate.