Troubleshooting and repair, Contactor test (continued), Caution – Lincoln Electric LN-15 WIRE FEEDER SVM166-A User Manual

Page 56

Advertising
background image

LN-15

F-18

F-18

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

TROUBLESHOOTING AND REPAIR

LARGE TERMINAL
STUDS

LEADS 507 & 578 (blue)

CONTACTOR TEST

(continued)

FIGURE F.5 – CONTACTOR

TEST PROCEDURE

1. Remove input power to the LN-15.

2. Perform the Wire Drive Assembly

removal procedure.

3. Locate the contactor and leads 507

and 578 (blue) and separate the two
in line connectors. See Figure F.5.

4. Apply 12 VDC to the contactor coil

leads.

Do not leave the 12 VDC applied to the
contactor coil for a prolonged period of
time (15 seconds maximum). Damage to
contactor may result.

5. If the contactor does not activate

when the 12 VDC is applied, the
contactor is faulty. Replace.

Note: The normal contactor coil resistance

is approximately 4.4 ohms.

6. If the contactor activates when the 12

VDC is applied, check the resistance
between the two large terminal studs
with the contactor activated. The
resistance should be very low (0 to
1 ohm).

7. If the resistance is “high” or “open”

between the two large terminal studs
when the contactor is activated, the
contactor is faulty. Replace.

8. If the contactor activates and the

resistance between the terminals is
low when the 12 VDC is applied, the
contactor is good.

NOTE: When the contactor is not activated,

the resistance between the terminals
should be very high (infinite). If the
resistance is always low, the
contacts are “stuck” and the
contactor is faulty. Replace.

CAUTION

Advertising