Troubleshooting & repair, Input contactor test (continued), Test for contact continuity – Lincoln Electric IDEALARC SVM136-A User Manual

Page 55: F-15, Figure f.4 – input contactor test connections

Advertising
background image

TEST FOR CONTACT CONTINUITY

1. Disconnect the main input supply power to the

machine.

2. Remove the two leads connected to the input con-

tactor coil, #233 and X1/#232. See Figure F.4 for
location.

3. Using the external 120VAC supply, apply 120VAC to

the terminals of the input contactor coil. If the con-
tactor does NOT activate, the input contactor is
faulty. Replace the input contactor.

4. With the contactor activated, check the continuity

across the contacts. (Zero ohms or very low resis-
tance is normal.) See Figure F.4. If the resistance
is high, the input contactor is faulty. Replace the
input contactor.

5. When the contactor is NOT activated, the resistance

should be infinite or very high across the contacts.
If the resistance is low, the input contactor is faulty.
Replace the input contactor.

TROUBLESHOOTING & REPAIR

F-15

F-15

IDEALARC CV-400

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Section TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

Retur

n to Master TOC

INPUT CONTACTOR TEST

(continued)

FIGURE F.4 – INPUT CONTACTOR TEST CONNECTIONS

#233

APPLY EXTERNAL
120 VAC HERE
(X1, #232 AND #233
LEAD TERMINALS)

U

V

W

(L1) (L2) (L3)

AH# A

CC730 - 8025B

(3186-30J755 18H)

LINCOLN ELECTRIC CO

.

CRI

SA M - 12161 - 61

LR49598 0597

X1, #232

U

V

W

(L1) (L2) (L3)

AH# A

CC730 - 8025B

(3186-30J755 18H)

LINCOLN ELECTRIC CO

.

CRI

SA M - 12161 - 61

LR49598 0597

Advertising