Typical Toggle Mode Wiring

For devices triggered by a normally open circuit, wire the contacts of the Main
and Auxiliary Relays in parallel (see the Figure below). Either relay will be able to
trigger the access device. Entry codes programmed for the Auxiliary Relay will be
able to hold the output on.

Select Door Sense or Inhibit Input

Default: Door Sense

The input on Terminal #14 can be programmed for DOOR SENSE or INHIBIT.

Press: 1 0 # Input#

Input = 0 for Door Sense, = 1 for Inhibit

When programmed for DOOR SENSE, if an open condition on the input occurs
before access is granted (with an entry code, transmitter or with the request-to-
enter input) a FORCED ENTRY output will occur. If an open condition remains 60
seconds after a relay activation for access, a DOOR AJAR output will occur.

When programmed for INHIBIT, a closed condition on the input will prevent
Relay #1 from activating when access is requested (with an entry code or
transmitter). This mode is typically used with an external timer to disable the
access device at certain times.

Select Forced Entry Output

Default: Output #3

Sets which output activates if the DOOR SENSE input opens before access is
granted. This output is not timed.

Press: 1 1 # Output #

Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Select Door Ajar Output

Default: Output #4

Sets which output activates if the DOOR SENSE input stays open 60 seconds after
access is granted. This output is not timed.

Press: 1 2 # Output #

Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Select Keypad Lockout Output

Default: No Output

Sets which output activates when the keypad is “locked out” after too many
incorrect entry code attempts. The lockout time is 60 seconds.

Press: 1 3 # Output #

Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

Select Keypad Active Output

Default: No Output

Sets which output activates when any keys are pressed. This output is timed. If
toggle mode is selected for the output, the timer value defaults to 2 seconds.

Press: 1 4 # Output #

Output = Output to Activate (0-4)

1 = Relay #1 2 = Relay #2 3 = Output #3 4 = Output #4 0 = No Output

217350 D IMAGE 11

N.O.

COMMON

N.C.

N.O.

COMMON

N.C.

MAIN

RELAY

AUXILIARY

RELAY

AKR-1

OUTPUTS

ACCESS

DEVICE

EITHER RELAY CAN TRIGGER
THE ACCESS DEVICE