14 stove installation, Alcove installation requirements – Lopi Leyden 028-S-75-2 User Manual

Page 14

Advertising
background image

14

Stove Installation

(for qualified installers only)

© Travis Industries

100-01177

4060802

Alcove Installation Requirements

Whenever the stove is placed in a location where the ceiling height is less than 8' tall, it is considered an
alcove installation. Because of the reduced height, the special installation requirements listed below must
be met.

Chimney connector and chimney must be one of the following types:

AMERI-TEC model DCC connector with AMERI-TEC UL 103 HT chimney
DURAVENT model DVL connector with DURAVENT UL 103 HT chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel HP connector with I.C.C. UL 103 HT chimney
METALFAB model DW connector with METALFAB UL 103 HT chimney
OLIVER MACLEOD PROVENT model PV connector with OLIVER MACLEOD UL 103 HT chimney
SECURITY model DP connector with SECURITY UL 103 HT chimney
SELKIRK model DSP connector with SELKIRK UL 103 HT chimney
Standard Masonry Chimney with any one of the above listed connectors

NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.

The clearances below must be met:

Minimum Clearance
(See
Figure 10 below)

Combustible

Alcove

A

Sidewall to stove

18.00"

B

Backwall to stove

20.75"

D

Connector to sidewall

28.25"

E

Connector to backwall

14.00"

G

Maximum depth of alcove

48.00"

H

Minimum width of alcove

63.25"

J

Minimum height of alcove

84.00"

a

d

e

h

j

g

b

Figure 10