Service Manual 27

Troubleshooting Guide

Possible Trouble 2

The compressor does not operate.

Possible Trouble 3

The compressor always operate.

Is setting

Temp. set lower than Room

Temp.-0.5

°

C?

Is the voltage No.10

of IC01M 0V?

• Replace IC01M.

• Select the setting Temp. to lower Number.

• Wait 3 Minutes.

Does the Unit delay

for 3 minutes?

• Replace MAIN

PCB Ass'y.

Is the voltage N0.9 of

IC01M DC 12V?

• Check the RY-COMP.

• Check the wiring

Diagram.

NO

NO

NO

YES

YES

YES

YES

Is the wire connection of

RY-COMP OK?

• Check the RY-COMP.

• Connect LEAD Wire to

RY-COMP again.

NO

YES

NO