Introduction

5

I - Digital output

loss-of-power

jumper

One of four output jumpers. Each digital output has a

jumper to set the fail-safe position of the output point when

power fails. The OFF position makes the contact Normally

Open (factory default). The ON position makes the contact

Normally Closed.
Note: The jumper position has no effect on the contact

when the AC4 has power.

3.2.3: Setting the Digital Output

Jumpers

7.6.4: Configure Output for Loss of

Power (“Fail-Safe”)

J - Digital input

connectors

Each of the four input connections is a two-state point: ON/

OFF (energized/de-energized).
An example of a field digital input is a Liebert

Environmental unit’s common alarm relay output.

3.0:

Wiring and Connections

3.2.1: Connecting Digital Inputs
5.4:

View Input Status

7.3:

Setup System - Setup Inputs

K - Digital input

status LEDs

Each input has an LED to indicate its status: ON/OFF

(energized/de-energized).

1.7:

LED Indicators

L - Serial interface

connector (RS232/

EIA574)

Connection for laptop or video terminal. Used for

configuration and monitoring using the Service Terminal

Interface. Requires a null modem cable for connectivity

(P/N 201258P1).

3.4:

RS232 Connector

A.2: Connecting to the Service

Terminal Interface

M - DIP switch 1

DIP switch used for resetting password to default.

7.7.1: Change Password

N - LCD connector

Connection for the LCD on the enclosure door.

N/A

O - LCD contrast

adjustment

Adjustment contrast for the LCD on the enclosure door.

N/A

P - 24VAC power

connector

Power connection for the controller. Requires 24VAC.

2.4:

Connect Power to the AC4

Table 1

Controller board components (continued)

Item

Description

For more information, see: