System and Control Options

32

7.5

Setup System - Setup Zones

The AC4 has two zones that may be used to define different areas—rooms or sections of a room. The

AC4 effectively performs as two separate units, controlling each zone separately, for examply, using a

different rotation sequence for devices in each zone.
Each zone may have two to four outputs associated with it. By default, Zone 1 has four associated out-

puts and Zone 2 has none.
To set up zones:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select Setup Zones

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Zones and press Enter

.

7.5.1 Set Up a Zone

• From the Setup Zones Menu, choose a zone—for example,

Zone 1—and press Enter

.

• On the Number of Devices screen, Use the arrows

↑↓

to select the

number of outputs for this zone, then press Enter

. The example

at right shows four outputs in Zone 1.

Table 15 shows the default number of outputs for each zone.

NOTE: Each zone that is used must have at least two outputs, and the

total for the two zones cannot exceed four.
A message appears if you enter too few or too many devices, as shown

at right. Press Escape to return to the Setup Zones menu.
Table 16 shows the possible combinations of outputs for each zone.

For example, if Zone 1 has four outputs, then Zone 2 may not be used

(0 outputs).

Table 15

Default zones

Zone

Default number of outputs

Zone 1

4

Zone 2

0

Table 16

Possible combinations - outputs per zone

If Zone 1 has:

Zone 2 must have:

4 or 3 outputs

0 (not used)

2 outputs

0 (not used) or 2 outputs

0 (not used)

2 or 3 or 4 outputs

Setup System Menu

SETUP INPUTS
SETUP COMMON ALARM

> SETUP ZONES

↑↓

=NEXT

=SELECT

SETUP OUTPUTS
SETUP SYSTEM INFO
SETUP OPERATION

Setup Zones

SETUP ZONES

> ZONE 1 4

ZONE 2 0

↑↓

=NEXT

=SELECT

Number of Devices

# DEVICES IN ZONE

ZONE 1

4

↑↓

=SELECT

=NEXT/END

Message (if too few

devices entered)

MINIMUM OF 2 DEVICES
ESC BACK

Message (if too many

devices entered)

TOO MANY DEVICES
ESC BACK