System and Control Options

28

7.2

Setup System - Overview

The Setup System screen displays six options that allow you to configure input and output devices,

the common alarm, and a variety of system details, such as login password and system date and time:

• Setup Inputs
• Setup Common Alarm
• Setup Zones
• Setup Outputs
• Setup System Info
• Setup Operation

7.3

Setup System - Setup Inputs

The AC4 has four digital input points that may be configured individ-

ually. These inputs may have a wide variety of Liebert or other manu-

facturers’ equipment connected.
To configure a digital input:

Log In and Choose Setup System

• From the Main Menu, use the arrows

↑↓

to

choose System and

Control, then press Enter

(see 7.1 - Login for help)

.

• Enter your password at the Login screen.
• From the System and Control Menu, use the arrows

↑↓

to

choose

Setup System, then press Enter

.

Select a Digital Input to Configure

• From the Setup System Menu, shown at right, use the arrows

↑↓

to

choose Setup Inputs and

press Enter

.

• From the Select Input Menu, choose an input—for example, Device_1—and press Enter

.

Table 13 shows the digital input features you may change, along with the default settings: you may

change the name of the input, define it as normally open or closed, and specify it as alarmable or as an

event.

• Alarmable inputs may be defined as either Unlatched or Latched.
• Event status allows you to monitor a digital input’s state—and use a change in state to initiate an

action through an output, if desired—without triggering an alarm. Events are always Unlatched.

• You may also specify a time delay before the AC4 responds to an alarm or event.

Use the steps following Table 13 to change the default settings for any digital input.
Table 13

Default settings - digital inputs

Feature

Default

Other Options

LABEL

DEVICE_1

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

L (Latched) / Y (Yes)*

NL (Unlatched) / N (No)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

Settings - Select Input Menu
(see Section 7.3)

When configuring an input
(see Section 7.3.4)

Unlatched

NL (Not Latched)

N (No, not latched)

Latched

L (Latched)

Y (Yes, latched)

Setup System Menu

> SETUP INPUTS

SETUP COMMON ALARM
SETUP ZONES

↑↓

=NEXT

=SELECT

SETUP OUTPUTS
SETUP SYSTEM INFO
SETUP OPERATION

Select Input Menu

SELECT INPUT

> DEVICE_1 NO-AL-NL

DEVICE_2 NO-AL-NL

↑↓

=NEXT

=SELECT

DEVICE_3 NO-AL-NL
DEVICE_4 NO-AL-NL