System and Control Options

34

7.6.2 Define Operating or Standby Mode

Each output may be defined as Operating (OP), Standby (ST), or Not

Used (NU). This setting takes precedence over any setting in the over-

ride menu (see 7.9 - Override Output).
Default settings are:

• Outputs 1, 2 and 3 are in Operating (OP) mode
• Output 4 is in Standby (ST) mode

To change the mode:

• From the Setup Outputs Menu, shown at right, use the arrows

↑↓

to

choose Mode for the selected output and press Enter

.

• To change the output’s mode, use the arrows

↑↓

to

choose one of

these options:

OP (Operating)
ST (Standby)
NU (Not Used)

• Press Enter

.

7.6.3 Enable or Disable an Output Device in Alarm Status

You may choose whether to Enable or Disable an output when the con-

nected device is in alarm status. The default setting for all output

points is Enabled.

• From the Setup Outputs Menu, choose In Alarm, as shown at

right, and press Enter

.

• To make a change, use the arrows

↑↓

to

choose E (Enable) or

D (Disable) to determine what happens when an alarm is detected

in the device.

• Press Enter

.

7.6.4 Configure Output for Loss of Power (“Fail-Safe”)

Each output has an associated jumper that can help prevent undesired effects when the controller

board loses power. For example, without the proper fail-safe jumper setting, a loss of power might

close a switch that is Normally Open (NO)—perhaps shutting off an environmental unit or a fan or

closing a valve.
This fail-safe jumper setting is unrelated to configuring an output as Normally Open (NO) or Nor-

mally Closed (NC), as described in 7.6.1 - Define Output as Normally Open or Normally Closed.
To configure a digital output jumper for a loss of power:

• Set the jumper in the “OFF” position (factory default) to make the output Normally Open (NO).
• Set the jumper in the “ON” position to make the output Normally Closed (NC).

For more information, see 3.2.3 - Setting the Digital Output Jumpers.

Setup Outputs Menu

SETUP DEVICE_1
NORM OPEN/CLOSE: NO

> MODE: OPERATING

↑↓

=NEXT

=SELECT

IN ALARM: ENABLE

Set Mode

SET MODE: OP

↑↓

=OP/ST/NU

=EDIT

Setup Outputs Menu

SETUP DEVICE_1
NORM OPEN/CLOSE: NO
MODE: OPERATING

↑↓

=NEXT

=SELECT

> IN ALARM: ENABLE

Change State in Alarm

STATE OF DEVICE
IN ALARM: DISABLE

↑↓

=E/D

=EDIT