2 view alarm log, 1 alarm log, Table 8 alarm log conditions – Liebert AC4 User Manual

Page 25: Viewing additional screens, View alarm log, Alarm log, Backing up the alarm log (service terminal, Table 8, Alarm log conditions

Advertising
background image

View Status Options

19

5.2

View Alarm Log

The Alarm Log contains up to 99 records of alarms that have occurred.

Records are added to this log as alarms occur.
To view the Alarm Log:

• From the Main Menu, use the arrows

↑↓

to

choose View Status,

then press Enter

↵.

• From the View Status Menu, use the arrows

↑↓

to

choose View

Alarm Log, then press Enter

.

5.2.1 Alarm Log

The Alarm Log screen displays up to 99 records showing alarm data,

including inputs and outputs in alarm status and failure of a standby

device. If the log contains any alarm records, the Alarm Log screen dis-

plays details for each alarm:

• the source of the alarm (for example,

DEVICE_1

)

• the status of an input or output (

CONTACT CLOSED

) or a brief descrip-

tion of the problem (

STNDBY DEVICE FAILED

)

• the date and time the alarm occurred

Table 8 shows conditions that the alarm log records for digital inputs

and in the panel itself.

If there are no alarms in the log, the screen displays the message:

NO ALARMS

Viewing Additional Screens

There may be up to 99 records of alarm data.

• To view additional records, use the arrows

↑↓

.

• To return to the previous screen, press the ESC key.

5.2.2 Backing Up the Alarm Log (Service Terminal Interface only)

The alarm log is stored as a file in the AC4; it can hold no more than 99 records. When the log is full,

the oldest records are deleted from the end of the file as new alarm records are added at the begin-

ning.
You may back up the alarm log file to a remote computer using the Service Terminal Interface, as

described in 6.2 - Back Up Log Files (Service Terminal Interface only).
To delete all records in the alarm log, see 7.10 - Clear Alarms & Logs.

Table 8

Alarm log conditions

SOURCE

Digital Input

Panel

CONDITIONS

RECORDED

ALARM

NORMAL

LOSS OF POWER

ALARM SILENCED

ALARMS CLEARED

STNDBY DEVICE FAILED

NO STANDBY AVAILABLE

NO RESTART AVAILABLE

Main Menu

> VIEW STATUS

SYSTEM AND CONTROL

↑↓

=NEXT

=SELECT

View Status Menu

VIEW ACTIVE ALARMS

> VIEW ALARM LOG

VIEW EVENT LOG
VIEW INPUT STATUS

VIEW OUTPUT STATUS

Alarm Log

> ALARM RECORD 99/99
DEVICE_1 ALARM
CONTACT CLOSED
30-JUN-04 09:29:10

NO STANDBY AVAILABLE

29-JUN-04 10:45:00

STNDBY DEVICE FAILED

29-JUN-04 10:39:00

NO RESTART AVAILABLE

28-JUN-04 06:54:09

Advertising