System and Control Options

30

7.3.4 Set Up Alarmable Inputs in Latched or Unlatched Mode

Alarmable input points may be set up in Latched mode (Y), which

requires the user to clear the AC4 alarms after an alarm has occurred,

or Unlatched mode (N), in which alarms will automatically clear after

a return-to-normal state. The default setting for alarmable inputs is

Y (Latched). Any input defined as an event is automatically

Unlatched.
An input defined as Latched does not reset automatically after an

alarm. It will remain in the triggered position even after the moni-

tored device returns to normal. After an alarm, the user must manu-

ally reset Latched inputs, as described in 7.10.1 - Clear Active

Alarms. This also means that any outputs linked to a Latched digital

input will remain triggered until the input is manually reset.
An input defined as Unlatched will automatically track the status of

the monitored device. No action by the user is required.

• From the Setup Inputs Menu, choose Latched, as shown above

right, and press Enter

.

• To change this feature, use the arrows

↑↓

to

choose Y (Yes -

Latched) or N (No - Unlatched), then press Enter

.

NOTE: Only alarmable input points may be set up as Latched. If you

attempt to set up an event as Latched, the message shown at right

appears. Press the ESC key to return to the previous screen to con-

tinue configuring the digital input.
The only way to reset latched alarms is by clearing active alarms. This

step is required to return latched points to their normal state. For

details, see 7.10.1 - Clear Active Alarms.

7.3.5 Set Up Delay Time

Each input may be set up with a specified time delay between the

occurrence of an alarm or event—a monitored device changes state—

and any response by the AC4. This feature can prevent needless

responses to transient conditions.
This delay is the amount of time that must elapse before the AC4

acknowledges the change of state in the monitored device and takes

any further action, such as dialing configured pagers. The default time

delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies only when a monitored device changes from its

normal state—for example, the AC4 detects a closed contact that is

defined as Normally Open.
When the monitored device returns to its normal state, the AC4

acknowledges the change of state after the delay timer ends its

countdown.

• From the Setup Inputs Menu, choose Delay, as shown at right, and press Enter

.

• To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):

• For minutes (MIN), press and hold one of the arrow keys

↑↓

scroll through the numbers 00-99.

• Press Enter

to advance to seconds (SEC).

• For seconds (SEC), press and hold one of the arrow keys

↑↓

scroll through the numbers 00-59.

• When finished, press Enter

again.

Setup Inputs Menu

SETUP DEVICE_1

LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL

↑↓

=NEXT

=SELECT

> LATCHED: N

DELAY: 00:01

Latched / Unlatched

IS ALARM
LATCHED? N

↑↓

=Y/N

=END

Message (if input has

been defined as an event)

LATCH NOT ALLOWED
WHEN IN EVENT MODE

ESC=BACK

Setup Inputs Menu

SETUP DEVICE_1

LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL

↑↓

=NEXT

=SELECT

LATCHED: N
DELAY: 00:01

Delay Time

DELAY TIME BEFORE
TRIGGER?

00 MIN : 01 SEC

↑↓

=SELECT

=NEXT/END