Warning – PB Heat 211A User Manual

Page 32

Advertising
background image

30

CONNECT GAS PIPING

c. When piping bleed lines to outside, terminate the

tubing downward to prevent water from entering
the tubing, and protect the tubing termination
from any obstruction. Terminate the tubing
above and well away from normal breathing
level or building air intakes.

D. INSTALL GAS SUPPLY PIPING

1. Size the piping as required by the National Fuel Gas

Code, ANSI Z223.1/NFPA 54 and/or CAN/CGA
B149 Installation Codes or as required by local
codes.

a. Use Table 7.1 for sizing of natural gas for a

system pressure drop of 0.3 inch water
column (75 Pa).

2. The standard gas train is designed for a maximum

pressure of 1/2 psig (14 inches water column/3.5 kPa).
Make sure the system regulator will not allow a higher
pressure to the Gas Control Train under any
conditions.

3. The minimum gas supply pressure is listed on the

Boiler Rating Label. Make sure the system regulator
and the piping are sized and adjusted properly to
provide this pressure under all conditions.

4. Install a Service Valve, Sediment Trap and Ground

Joint Union at the supply connection to the Gas
Control Train as shown in Figure 7.2. These are not
supplied with the boiler. Install them in accordance
with local codes.

5. Use only pipe joint compounds rated for use with

Liquefied Petroleum Gases. This is necessary
because most natural gas contains propane as well
as methane.

E. TEST GAS SUPPLY PIPING

1. ISOLATE THE BOILER GAS CONTROL TRAIN

FROM THE SYSTEM DURING TEST:

a. Test pressure 1/2 psig (3.5 kPa) or less – Close

the Manual Shut-Off Valve on the Boiler Gas
Control Train

b. Test pressure over 1/2 psig (3.5 kPa) – Disconnect

the gas supply piping upstream of the Boiler
Manual Shut-Off Valve

Do not expose the Gas Control Train to excessive
pressure. The gas valves can be damaged. This could
result in explosion hazard and severe personal injury
or death.

Do not test gas supply piping with open flame. Use a
soap suds mixture brushed onto the pipe joints to
test for leaks.

WARNING

Figure 7.2: Gas Supply Connection to Boiler

Advertising