CONNECT GAS PIPING

Table 7.1: Capacity of Gas Supply Pipe in Cubic Feet (Cubic Meters) Per Hour of Natural Gas for

0.3 inch (75 Pa) Drop.

Above ratings based on natural gas with specific gravity of 0.60 allowing pressure drop of 0.3 inches (75 Pa). No allowance
is needed for pipe fittings. Use the following multipliers on above capacities for specific gravity other than 0.60:

Specific Gravity

0.50

0.55

0.60

0.65

0.70

Multiply Capacity by:

1.10

1.04

1.00

.962

.926

Pipe Length

1-1/4" Pipe

1-1/2" Pipe

2" Pipe

2-1/2" Pipe

3" Pipe

4" Pipe

6" Pipe

Feet

Meters

Foot

3

Meter

3

Foot

3

Meter

3

Foot

3

Meter

3

Foot

3

Meter

3

Foot

3

Meter

3

Foot

3

Meter

3

Foot

3

Meter

3

10

3.0

1050

30

1,600

45

3,050

86

4,800

136

8,500

241

17,500

496

44,000

1246

20

6.1

730

21

1,100

31

2,100

59

3,300

93

5,900

167

12,000

340

31,000

878

30

9.1

590

17

890

25

1,650

47

2,700

76

4,700

133

9,700

275

25,000

708

40

12.2

500

14

760

22

1,450

41

2,300

65

4,100

116

8,300

235

22,000

623

50

15.2

440

12

670

19

1,270

36

2,000

57

3,600

102

7,400

210

20,000

566

60

18.3

400

11

610

17

1,150

33

1,850

52

3,250

92

6,800

193

18,000

510

70

21.3

350

10

560

16

1,050

30

1,700

48

3,000

85

6,200

176

17,000

481

90

27.4

320

9

490

14

930

26

1,500

42

2,600

74

5,400

153

15,000

425

100

30.5

305

9

460

13

870

25

1,400

40

2,500

71

5,100

144

14,000

396

150

45.7

250

7

380

11

710

20

1,130

32

2,000

57

4,100

116

11,500

326