Preinstallation – PB Heat 211A User Manual

Page 6

Advertising
background image

4

i.

Where communicating directly or through
vertical ducts with the outdoors each opening
shall have a minimum free area of 1 in

2

per

4000 Btu/hr (22 cm

2

per 4000 W) of total

input rating for all equipment in the space.
See Figure 1.4 for openings directly
communicating with the outdoors or Figure
1.5 for openings connected by ducts to the
outdoors.

ii. Where communicating with the outdoors

through horizontal ducts, each opening shall
have a minimum free area of 1 in

2

per 2000

Btu/hr (22 cm

2

per 2000 W) of total rated

input for all appliances in the space. See
Figure 1.6.

b. One Permanent Opening Method: Provide

one permanent opening beginning within 12
inches (305 mm) of the top of the space. The
opening shall communicate directly with the
outdoors, communicate through a vertical or
horizontal duct, or communicate with a space
that freely communicates with the outdoors.
The opening shall have a minimum free area of
1 in

2

per 3000 Btu/hr of total rated input for all

appliances in the space and not less than the
sum of the cross-sectional areas of all vent
connectors in the space. The gas-fired equipment
shall have clearances of at least 1 inch (25 mm)
from the sides and back and 6 inches (150 mm)
from the front of the appliance. See Figure 1.7
for this arrangement.

Figure 1.4:

Air Openings – All Air Directly from
Outdoors

Figure 1.5:

Air Openings – All Air from Outdoors
through Vertical Ducts

Figure 1.6:

Air Openings – All Air from Outdoors
through Horizontal Ducts

Figure 1.7:

Air Openings – All Air from Outdoors
through One Opening

PREINSTALLATION