Troubleshooting – service tips – PB Heat 211A User Manual

Page 49

Advertising
background image

47

TROUBLESHOOTING – SERVICE TIPS

Problem

Possible Cause

Suggested Remedy

Main Gas Valve Opens

Manual Valve Closed at Gas Train

Open Valve

But No Gas Flows

Manual Valve Closed at Meter

Open Valve

Test Firing Valve Closed (if Provided)

Open Valve

Sags in Steam Piping or not enough Pitch

Correct Piping Condition

Concentric reducers causing condensate pooling

Correct Piping

Drip trap failed closed

Replace Trap or Trap Element

Water Hammer On Start-Up

Dry returns wetted due to new boiler water line

Correct Piping or Install Feed System and Traps

higher than old boiler

No drip line on the back side of a back-pitched

Install Drip Line and Trap

motorized valve

Clogged returns on gravity system

Clean or Re-Pipe Return Line(s)

Incorrect near-boiler piping causing wet steam

Correct Piping per Manual

to system

Trap failed open, allowing steam to enter returns

Replace Trap or Trap Element

{Radiator Hammer} Large radiator may be

Use smaller Air Vent or Use Two Small Vents in

vented too quickly

Place of One Large Vent, One Mounted Higher
than the Other

Long nipple at Hartford Loop

Replace with Close Nipple

Water Hammer During Mid-Cycle

Water leg or back slope in return line to receiver

Correct Piping

tank, causing water pocketing

Trap installed at receiver tank, causing water

Remove Trap at Tank, Installing Drip Traps and

trapping in return

Radiator Traps where Required

Boiler feed pump or condensate pump feed rate

Throttle Flow Rate

too fast, causing spraying into equalizer

No drip on the inlet side of a forward pitched

Add Drip Line and Trap

motorized valve

Uninsulated steam piping, causing excessive

Insulate Steam Pipes

condensate loads

Close nipple on Hartford too high

Repipe 2" to 4" (5cm to 10cm) Below Water Line

Water Hammer on Shut-Down

Uninsulated steam piping in boiler room, but
system piping insulated, causing vacuum

Insulate Steam Pipes

condition on shut-down

Hammering in the Boiler

Poor circulation in the boiler due to sludge

Clean and Blowdown the Boiler

accumulation

Main vents not working

Replace Main Vents, Repiping away from End
of Lines if Needed

Drip Traps failed closed

Replace Traps or Trap Elements

No Heat or Poor Heat Distribution

Radiator traps failed open, allowing pressurization

Replace Traps or Trap Elements

of the returns

in the Building

Water legs or back slope in return lines to receiver

Correct Piping

tank, preventing air from venting out receiver vent

Boiler pressure too high, causing air vents to lock

Reduce Operating Pressure

up or blowing water loop seals

New boiler water content smaller than old boiler

Install Boiler Feed System with Receiver Tank
Large enough for Condensate

Boiler water feed rate or pump rate too fast

System or Boiler Overfilling or Flooding

causing water level to collapse (due to collapse of

Reduce Feed Rate

steam bubbles in boiler water)

Foaming, priming or surging due to poor

Clean the Boiler

water quality

Poor water quality, causing foaming and surging

Clean the Boiler

Excessive Water Level Bounce

Incorrect near-boiler piping, such as undersized

Pipe per Manual

or incorrectly placed risers

Boiler water feed rate or pump rate too fast

Reduce Feed Rate

Air vents or traps not venting air, preventing
steam from getting to radiation and pressurizing

Replace Vents or Traps

Rapid Cycling

the air pocket

Pressure differential on pressure control too close

Adjust Control Differential

Nuisance outages of water level control due to

See Excessive Water Level Bounce Above

boiler water level bounce