Unsupervised, normally open – Pelco DX2000 User Manual

Page 23

Advertising
background image

Pelco Manual C690M-E (11/04)

23

Figure 8b. Unsupervised Alarm Operation

UNSUPERVISED, NORMALLY CLOSED

TIME

+5V

+5V

0.1uF

0.1uF

INPUT

VOLTAGE

STAND-BY MODE

2.5V

0V

POINT A

POINT A

10K

10K

100K

GND

GND

GND

EQUIPMENT SIDE

ALARM WIRING SIDE

NORMAL
CURRENT FL0W
NO ALARM

S

Processor
CIRCUITRY

GND

TTL-CMOS
EXTERNAL
CONTROL

< _

50ms

PIN 1

PIN 2

A L A R M

A L A R M

IN THIS CONFIGURATION, TRANSISTOR "S" (THE SWITCH) IS BIASED
FOR CONDUCTION AND POINT "A" RESIDES CLOSE TO 0V. IF THE
TRANSISTOR IS BIASED TO THE OFF STATE OR IF THE LINE IS CUT TO
STOP CURRENT FLOW, POINT "A" RISES TOWARD 5V AND AN ALARM
CONDITION.

NOTE: PIN NUMBERS
REFER TO TYPICAL
HEADER ALARM INPUT
NUMBERS ON MATING
PLUGS

NOTE: TIME DURATION
OF THE INPUT
CONTROL SIGNAL MUST
BE 50ms OR MORE

HIGH = STAND-BY MODE
LOW = ALARM

UNSUPERVISED, NORMALLY OPEN

TIME

+5V

+5V

0.1uF

0.1uF

INPUT

VOLTAGE

STAND-BY MODE

2.5V

0V

POINT A

POINT A

10K

10K

100K

GND

GND

GND

EQUIPMENT SIDE

ALARM WIRING SIDE

NORMAL
CURRENT FL0W
NO ALARM

S

Processor
CIRCUITRY

GND

TTL-CMOS
EXTERNAL
CONTROL

< _

50ms

PIN 1

PIN 2

A L A R M

A L A R M

IN THIS CONFIGURATION, TRANSISTOR "S" (THE SWITCH) IS BIASED
FOR NON- CONDUCTION AND POINT "A" RESIDES CLOSE TO 5V. IF AN
INPUT CONTROL SIGNAL OF SUFFICIENT DURATION TURNS ON THE
TRANSISTOR FOR ALARM ACTIVATION OR IF THE LINE IS SHORTED,
POINT "A" WILL FALL TOWARD 0V AND AN ALARM CONDITION.

NOTE: PIN NUMBERS
REFER TO TYPICAL
HEADER ALARM INPUT
NUMBERS ON MATING
PLUGS

NOTE: TIME DURATION
OF THE INPUT
CONTROL SIGNAL MUST
BE 50ms OR MORE

HIGH = ALARM
LOW = STAND-BY MODE