Configuration

18

Powerware

®

9120 User's Guide

S

05147426 A Uncontrolled Copy

5. To exit Configuration mode at any time, do not press any

buttons for five seconds. The UPS returns to Normal mode and

displays

On Line

.

B

Y

Press the Enter button to select a

parameter. Also press the Enter button to

select an option and to save the setting.

Press the Scroll button to enter

Configuration mode. Also press

to scroll to the next option.

LCD Panel

Figure 5. Using the Configuration Mode

Table 1. Configuration Mode Parameters

Parameter

LCD Message

Description

Default Settings

Output Voltage

Setting

O/P V Setting

To change the output voltage:

S Select 100, 110, 120, or 127V for 120V models.

S Select 200, 208, 220, 230, or 240V for 208V models.

S Select 208, 220, 230, or 240V for 230V models.

You are prompted to save this setting.

For 120V models:

O/P V= 120V

For 208V models:

O/P V= 208V

For 230V models:

O/P V= 230V

Input Voltage

Tolerance

I/P Bypass Set

Select the input voltage tolerance range before the

UPS goes to Battery mode: ±10%, +10%/-15%, or

+15%/-20%.

You are prompted to save this setting.

I/P Tol=+10%/-15%

Input Voltage

Frequency

I/P F Setting

The factory-default is 50 or 60 Hz, ±5%. Select ±2%

for a narrower frequency range. Select ±7% for a

wider frequency range.

You are prompted to save this setting.

Freq Tol.=+/-15%