UPS Maintenance

30

Powerware

®

9120 User's Guide

S

05147426 A Uncontrolled Copy

W

A

R

N

I

N

G

S

Batteries can present a risk of electrical shock or burn from high short circuit

current. The following precautions should be observed: 1) Remove watches, rings,

or other metal objects; 2) Use tools with insulated handles; 3) Do not lay tools or

metal parts on top of batteries.

S

ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or

connectors. Attempting to alter wiring can cause injury.

S

Replace batteries with the same number and type of batteries as originally

installed in the UPS.

S

DO NOT DISCONNECT the batteries while the UPS is in Battery mode.

How to Replace External Batteries

Use the following steps to replace external batteries:

1. Unplug the EBM cable from the UPS and the old battery.
2. Remove the old battery. See Recycling the Used Battery" on

page 32 for proper disposal.

3. Plug the EBM cable into the battery connector on the new

battery.

4. Plug the other end of the EBM cable into the UPS as shown in

Figure 13.

EBM

Battery

Connectors

UPS Battery

Connector

EBM

Cable

Figure 13. External Battery Connections (120V Model Shown)