Roubleshooting, Audible alarms and ups conditions, Silencing an audible alarm – Powerware 700 3000 VA User Manual

Page 43

Advertising
background image

37

Powerware

®

9120 User's Guide

S

05147426 A Uncontrolled Copy

C H A P T E R 8

T

ROUBLESHOOTING

This section explains:
S UPS alarms and conditions
S How to silence an alarm
S Service and support

Audible Alarms and UPS Conditions

The UPS has an audible alarm feature to alert you of potential power

problems. When the alarm is activated, the UPS beeps in different

intervals according to a particular condition. Use Table 10 to determine

and resolve the UPS alarms and conditions.

Silencing an Audible Alarm

There are two ways to silence the alarm for an existing fault:
S Press one of the front panel control buttons (

B

Y

, , or ).

S Turn the Alarm Silence option on through the front panel (see

Configuration Mode" on page 17).

If UPS status changes, the alarm beeps, overriding the previous alarm

silencing. The alarm does not silence if there is a low battery condition.

Table 10. Troubleshooting

LCD Message or

Condition

Possible Cause

Action

UPS does not turn on.

The UPS is not correctly

connected to the power source.

Check connections to the power source.

The wall outlet is faulty.

Have a qualified electrician test and repair the outlet.

The REPO connector is missing

or open.

Reconnect or close the REPO switch (see page 22). Restart

the UPS.

A circuit breaker or an input

fuse on the rear panel is open.

Push the circuit breaker button or replace the fuse. Restart

the UPS.