Configuration

20

Powerware

®

9120 User's Guide

S

05147426 A Uncontrolled Copy

Default Settings

Description

LCD Message

Parameter
Number of

Extended Battery

Modules

Bat Pack Num Set

Select the number of EBMs connected to the UPS:

S For 700ć1500 VA models, select 0 through 2.

S For 2000ć3000 VA models, select 0 through 5.

You are prompted to save this setting.

Extern Pack: 0

Communications

Lock-out

COM Control Cmds For greater levels of security, users may choose to

have the UPS disregard shutdown commands that

come from the power management software or other

communication sources.

S When disabled, the UPS does not accept a shut

down command via the communication port, USB

port, or communication slot adapter.

S When enabled, the UPS operates normally in

response to external commands.

You are prompted to save this setting.

Enable

Load Segment

Control

Load Group Set

Allows manual control of load segments (see Load

Segments" on page 24).

By repeatedly pressing the scroll button, the individual

load segments can be turned on and off.

CAUTION

To prevent the unintentional shutdown of

specific load segments, confirm your selection before

pressing the button.

Group 1On 2On

Manual Bypass

Manual Bypass GO This parameter is used to manually place the UPS in

Bypass mode.

Bypass OFF

Configuration Mode

Setting

Config Mode Set

This parameter is reserved for future use, and should

not be modified by the user. The setting may be

toggled between

EscapeConfigMode

and

Enter

ConfigMode

. It should always be set to

EscapeConfigMode

.

EscapeConfigMode