Powerware 700 3000 VA User Manual

Page 45

Advertising
background image

Troubleshooting

39

Powerware

®

9120 User's Guide

S

05147426 A Uncontrolled Copy

Action

Possible Cause

LCD Message or

Condition

Battery Overload

2 beeps per second.

The UPS is on battery, and the

power requirements exceed

UPS capacity (130% for

10 seconds or >130% for

1.5 seconds) or the load is

defective.

Shutdown is imminent (30 seconds). Save your work and

turn off your equipment. Turn off and unplug or remove

utility power from the UPS. Remove some of the equipment

from the UPS. Restart the UPS. You may need to obtain a

larger capacity UPS.

Site Fault

1 beep per second.

Ground wire connection does

not exist or the line and neutral

wires are reversed in the wall

outlet.

Have a qualified electrician correct the wiring.

To disable this alarm, see Configuration Mode" on page 17.

Battery Test

The UPS is performing a battery

test.

None. The UPS returns to Normal mode when it completes a

successful battery test.

Over-Temperature

Constant beep.

UPS internal temperature is too

high.

Shutdown is imminent. Save your work and turn off your

equipment. Turn off the UPS.

Clear vents and remove any heat sources. Ensure the airflow

around the UPS is not restricted. Wait at least 5 minutes and

restart the UPS. If the condition persists, contact your

service representative.

Over-Charge

Constant beep.

Batteries are over-charged.

Save your work and turn off your equipment. Turn off the

UPS. Contact your service representative.

Charger Failure

Charger has failed.

Save your work and turn off your equipment. Turn off the

UPS. Contact your service representative.

Output Short

Constant beep.

Output short circuit.

Save your work and turn off your equipment. Turn off the

UPS. Contact your service representative.

High Output Voltage

Constant beep.

High output voltage.

Save your work and turn off your equipment. Turn off the

UPS. Contact your service representative.

Low Output Voltage

Constant beep.

Low output voltage.

Save your work and turn off your equipment. Turn off the

UPS. Contact your service representative.

High DC Bus

2 beeps per second.

High internal DC bus voltage.

Save your work and turn off your equipment. Turn off the

UPS. Contact your service representative.