Communication port – Powerware 700 3000 VA User Manual

Page 32

Advertising
background image

Additional UPS Features

26

Powerware

®

9120 User's Guide

S

05147426 A Uncontrolled Copy

Communication Port

To establish communication between the UPS and a computer, connect

your computer to the UPS communication port using the supplied

communication cable.
When the communication cable is installed, power management

software can exchange data with the UPS. The software polls the UPS for

detailed information on the status of the power environment. If a power

emergency occurs, the software initiates the saving of all data and an

orderly shutdown of the equipment.
The cable pins are identified in Figure 12 and the pin functions are

described in Table 2.

3

8

7

9

1

6

2

4

5

Figure 12. Communication Port

Table 2. Communication Port Pin Assignment

Pin

Number

Signal Name Function

Direction from

the Multi-Port

Module

1

Low Batt

Low Battery relay contact

Out

2

RxD

Transmit to external device

Out

3

TxD

Receive from external device

In

RS-232 low

level signal for

>0.4 seconds

Conditional Power Off: In absence of AC

power, output is turned off until normal AC

power returns

In

4

Ċ

No Connection

Ċ

5

GND

Signal Ground

Ċ

6

Ċ

No Connection

Ċ

7

Ċ

No Connection

Ċ

8

AC Fail

AC Fail relay contact

Out

9

Power Source

+V (8 to 24 volts DC power)

Out