36

Powerware

®

9120 User's Guide

S

05147426 A Uncontrolled Copy

Table 8. Battery

Configuration

700 VA: (2) 12V, 7 Ah internal batteries; 24 Vdc

1000 VA: (3) 12V, 7 Ah internal batteries; 36 Vdc

1500 VA: (4) 12V, 7 Ah internal batteries; 48 Vdc

2000ć3000 VA: (8) 12V, 7 Ah internal batteries; 96 Vdc

EBM Configuration

PW9120 BAT-700: (4) 12V, 2 7 Ah; 24 Vdc
PW9120 BAT-1000: (6) 12V, 2 7 Ah; 36 Vdc
PW9120 BAT-1500: (8) 12V, 2 7 Ah; 48 Vdc
PW9120 BAT-3000: (16) 12V, 2 7 Ah; 96 Vdc

Type

Sealed, maintenanceĆfree, valveĆregulated, leadĆacid

Charging

Approximately 4 hours to 90% usable capacity at nominal line voltage after full load discharge

Table 9. Battery Run Times (in Minutes)

Number of Batteries

Run Times at Full/Half Load by UPS VA Ratings

Number of Batteries

700 VA

1000 VA

1500 VA

2000 VA

3000 VA

UPS Internal Batteries

7/18

7/18

7/18

12/34

6/15

1 EBM

34/70

36/80

29/67

49/107

30/70

2 EBMs

64/140

66/155

56/130

93/195

58/128

3 EBMs

141/310

87/191

4 EBMs

192/403

120/264

5 EBMs

240/504

148/325

NOTE

Battery times are approximate and vary depending on the load configuration and battery charge.