D. INSTALL COILS OR PLATES

1. Remove the coil cover plates, gaskets and mounting

hardware, located in the Flue Box Carton.

2. Install tankless heaters, if used, in openings #1 and

#2. See Figure 2.10 and Table 2.2.

3. Place the cover plates and gaskets over any unused

heater openings. Place the cover plate with two 3/4"
NPT tappings on the upper flow port opening
(Position #2) of the Front Section.

E. HYDROSTATIC TEST THE BOILER

1. Install a drain valve in the Rear Section, Tapping 13.

See Figure 8.2.

2. Provide a water supply line to the boiler.

3. Plug all open tappings in the boiler.

4. Provide a means to vent air as the boiler fills.

5. Fill the boiler with water, venting air as water level

rises.

6. Pressurize boiler to:

• 75 psig for 50 psig sections.
• 120 psig for 80 psig sections.
• DO NOT EXCEED THESE PRESSURES.

a) Maintain pressure while checking all joints and

fittings for leaks.

7. After inspection is complete, drain the boiler and

remove plugs from tappings that are to be used.

17

PLACE THE BOILER

Table 2.2: Tankless Coil Ratings

LC-04

LC-05R

LC-05
LC-06
LC-07
LC-08
LC-09
LC-10
LC-11
LC-12

LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24

Model

GPM

Location

5.5

5.62
5.75
6.25

6.5
7.0

7.25

7.5
8.0













2
2
2
2
2
2
2
2
2












GPM

Location

6.5
7.0

7.75

8.5

9.25
10.0

10.75
11.50
12.25

13
13
13
13
13
13
13
13
13
13
13
13


2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

GPM

Location




13.0

13.75

14.5
15.5
16.5
17.5
18.0

18.75

19.5

20
20
20
20
20
20
20
20
20





2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2

GPM

Location

8.0
9.0

10.0
12.0
13.0
14.0
14.5
15.0
16.0













1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2













GPM

Location

9.5

10.5
13.0
15.5
17.5
20.0
21.5
23.5
24.5

26
26
26
26
26
26
26
26
26
26
26
26

1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2

GPM

Location




15.5
18.0
20.0
22.5
24.5
27.0

29

31.5
33.5
35.5
37.5
39.5

40
40
40
40
40
40




1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2
1 & 2

Figure 2.10: Tankless Coil Openings

Heater No.

X-1020

Heater No.

X-1021

Heater No.

X-1022

Two Heaters No.

X-1020

Two Heaters No.

X-1021

Two Heaters No.

X-1022

Above heater ratings are based on intermittent demand for water from 40

°

F to 140

°

F with 200

°

F boiler water.

DANGER: Install mixing valve in hot water supply piping. Water temperature over 125°F can cause severe burns instantly or death from scalds.