Venting, Install the burner – PB Heat Gas/Oil Boilers User Manual

Page 31

Advertising
background image

29

VENTING

5. VENTING

Refer to Chapter 1, Preinstallation, Section D. Chimney
or Vent for installation requirements. Refer to
Chapter 9, Starting the Boiler, Section C. Run Burner
Check Out for damper settings and draft requirements.

6. INSTALL THE BURNER

A. BURNER APPLICATION

1. Refer to Burner Spec and Data Sheets for the Oil

and Gas/Oil Burners pre-tested with Series LC
boilers.

2. Make sure the nozzle sizing and spray pattern match

those given in the spec and data sheets.

3. See Figure 6.1 and Table 6.1 for combustion

chamber dimensions.

B. INSTALL BURNER MOUNTING PLATE

1. The Burner Mounting Plate is made to fit the burner

being used. Burners vary in bolt pattern for the
flange, burner tube diameter, insertion length and
near-tube configuration. Make sure the front plate is
correct for your burner if purchased separately from
the boiler.

2. Remove the Burner Mounting Plate and Hardware

Bag from the crate.

3. Screw (7) 3/8"-16 x 2 1/4" studs into the holes in the

front section around the chamber opening.

4. Secure the Burner Mounting Plate to the front

section with the flat washers and hex nuts.

C. MOUNT THE BURNER

1. Remove the Burner from its crate. Read the burner

instructions.

2. Insert (4) 3/8"-16 x 1 1/4" studs supplied with Burner

Mounting Plate into the front plate holes.

3. Place the high temperature gasket on the burner

front plate and secure the burner to the front plate
with 3/8" flat washers and hex nuts.

4. If the burner is supplied with a pedestal, install it to

the burner per the Burner Manufacturer’s
Instructions. The pedestal provides additional
support and prevents the burner from sagging.

Advertising