Starting the boiler – PB Heat Gas/Oil Boilers User Manual

Page 40

Advertising
background image

4. Adjust the burner as needed for a CO2 reading of:

a) Oil burners: CO2 approximately 12.5% or 1%

less than the level at which the smoke reading
goes above a trace on the Bacharach scale.

b) Gas burners: 9% to 10% with CO less than 50

ppm.

c) Inspect all flue gas joints (sections, attachments,

breeching and vent) for gas tightness. Remove
the jacket panels in order to thoroughly inspect
all rope seal joints between the sections.

D. CHECK BOILER CONTROLS

1. Limit and Operating Temperature Controls

a) Lower the setting of each control until the burner

shuts down.

2. Low Water Cutoffs

a) Test probe type controls by using the Push-to-Test

Button.

b) Test float type controls. ASME CSD-1 requires

the control to be piped with Test-n-Check valves
in order to allow isolation for test.

3. Follow additional instructions in the Burner Manual

for proving the burner component operation.

4. Check all controls to make sure they function

correctly.

5. After all controls have been proven, set the

Operating and High Limit Temperature Controls to
the temperatures desired.

38

STARTING THE BOILER

Table 9.1: Typical Combustion Chamber Pressure and Boiler Draft Loss

LC-04

LC-05R

LC-05
LC-06
LC-07
LC-08
LC-09
LC-10
LC-11
LC-12

LCE-13
LCE-14
LCE-15
LCE-16
LCE-17
LCE-18
LCE-19
LCE-20
LCE-21
LCE-22
LCE-23
LCE-24

+ 0.22
+ 0.22
+ 0.24
+ 0.26
+ 0.27
+ 0.28
+ 0.29
+ 0.30
+ 0.31
+ 0.32
+ 0.24
+ 0.25
+ 0.26
+ 0.27
+ 0.28
+ 0.29
+ 0.30
+ 0.31
+ 0.31
+ 0.31
+ 0.32
+ 0.32

Model

Boiler Draft Loss

(Inches w.c.)

Combustion Chamber Pressure

with 0.1” w.c. at Rear Flue Box Test Port

(Inches w.c.)

0.12
0.12
0.14
0.16
0.17
0.18
0.19
0.20
0.21
0.22
0.14
0.15
0.16
0.17
0.18
0.19
0.20
0.21
0.21
0.21
0.22
0.22

NOTE: Actual chamber pressure and draft loss readings may vary with each boiler and installation due to variation in the heat exchanger,
deposits in the flueways, actual burner firing rate and excess air conditions. Use the above numbers as a general guide only. If the measured draft
loss is considerably higher than the above, check the flueways for deposits and confirm the burner firing rate.