Warning – PB Heat Gas/Oil Boilers User Manual

Page 5

Advertising
background image

B. CLEARANCE FROM COMBUSTIBLE

CONSTRUCTION

Provide the following minimum clearances to
combustible construction
. See Figure 1.1.

1. Sides: 6"

2. Rear of Jacket: 6"

3. Front of Jacket: 24"

4. Top of Jacket: 24"

5. Hot Water Pipes: 6"

6. Vent or Chimney Connector: 18"

C. COMBUSTION AND VENTILATION AIR

1. The installation must provide adequate air for

combustion and ventilation.

2. Unless the boiler room construction and natural air

infiltration are sure to provide all the air needed,
provide an opening or duct to the outside with a free
cross sectional area of at least 1 square inch per
4000 Btuh input for all installed appliances. At high
altitude, increase this requirement 4% for each 1000
feet above sea level.

3. The boiler room must never be under negative

pressure. If exhaust fans or other equipment can
cause a negative pressure in the boiler room, the air
openings and equipment design must be engineered
to assure a neutral or slightly positive pressure in the
boiler room at all times of operation. If the
equipment design and air openings cannot assure
this, then the boiler must be located in an isolated
room.

4. Using combustion air dampers:

a) If motorized dampers are used on the

combustion and ventilation air openings, wire
them such that they must open when the boiler
tries to operate. They must include a switch
which prevents the boiler from operating if they
do not open. See Figure 1.2.

D. CHIMNEY OR VENT

1. Inspect the existing chimney or vent system. Make

sure it is in good condition. Inspect chimney liner
and repair or replace if necessary.

2. The vent system and installation must be in

accordance with the current edition of the American
National Standard ANSI/NFPA 211, “Chimneys,
Fireplaces, Vents, and Solid Fuel Burning
Appliances”, or applicable provisions of the local
building codes. The venting requirements for the
LCE are the same as for the LC. Figure 1.3 shows
the top flue outlet required on LCE boilers.

3. Chimney/Vent Operation: The vent system must be

sized and installed to remove all combustion
products. If the vent system is not sized properly, the
burner may not operate properly. This can cause
poor combustion or sooting to occur.

4. If the vent terminates in an area where wind-

generated downdrafts are likely, install a suitable vent
cap which can control wind effects.

5. This boiler is designed to fire only with a pressurized

fire box. The breeching and vent may be sized for
negative, neutral or positive pressure (no more than
0.l inches water column at the boiler outlet) as
desired. But negative pressure overfire can cause
lifting of the flame and poor combustion or
overheating of the boiler crown sheet.

6. Forced draft breechings and vents must be sealed

and of heavy gauge steel construction and must
comply with all applicable codes of construction.

7. The vent diameter and minimum height for stub

vents are listed in the Ratings and Dimensions
Section of this manual. Always extend vent
terminations at least 3 feet above the roof line. See
Figure 1.3.

3

PREINSTALLATION

Figure 1.2: Motorized Vent Damper Interlock

Figure 1.3: Vent Termination, Typical

Failure to provide adequate venting can result in
severe property damage, personal injury or death.

WARNING

Advertising