VENTING, INLET AIR AND CONDENSATE

D. EXHAUST VENT AND INTAKE AIR PIPE

SIZING

1. For the PI-T50 and PI-T80 Boilers the exhaust vent

and air intake pipes should be 2" Schedule 40 or 80.

2. For the PI-80, PI-140, PI-199 the exhaust vent and

air intake pipes should be 3" Schedule 40 or 80.

3. The total combined equivalent length of exhaust

vent and intake air pipe should not exceed 85 feet.

a. The equivalent length of elbows, tees, and other

fittings are listed in Table 5.1.

b. For example: If the exhaust vent has two 90°

elbows and 10 feet of PVC pipe we will
calculate:

Exhaust Vent Pipe Equivalent Length = (2x5)+10=20 feet

Further, if the intake air pipe has two 90° elbows,
one 45° elbow and 10 feet of PVC pipe, the
following calculation applies:

Air Intake Pipe Equivalent Length = (2x5)+3+10=23 feet

Finally, if a concentric vent kit is used we find:

Total Combined Equivalent Length = 20+23+3=46 feet

Therefore, the total combined equivalent length
is 46 feet which is well below the maximum of
85 feet.

c. The intake air pipe and the exhaust vent are

intended to penetrate the same wall or roof of
the building.

d. Effort should be made to keep a minimum

difference in equivalent length between the air
intake pipe and the exhaust vent.

Figure 5.1: Location of exit terminals of mechanical draft and direct-vent venting systems.
(Reference: National Fuel Gas Code ANSI Z223.1/NFPA 54 2002).

Fitting Description

Equivalent Length

Elbow, 90°, Short Radius

5

Elbow, 45°, Short Radius

3

Coupling

0

Air Intake Tee

0

Concentric Vent Kit

3

V1000 & V500 Vent Kit

0

Table 5.1: Fitting Equivalent Length Table

Figure 5.2:

Multiple Pinnacle Vent Spacing