Notice – PB Heat Gas Boiler User Manual

Page 9

Advertising
background image

7

c. The required flow rate can be calculated based

on the design temperature difference from the
return to the supply of the boiler. For a PI-T80
with a design temperature difference of 20°F the
calculation is as follows:

d. Table 3.3 shows the pressure drop (in feet of

water) for a flow rate which gives a 20°F
temperature difference for each boiler model.

e. The boiler pressure drop for various flow rates

can be determined by using Figure 3.2, the
Pinnacle Circulator Sizing Graph.

f.

Table 3.4 gives the recommended circulators for
a boiler on a secondary loop with water as the
heating medium.

g. Special consideration must be given if anti-freeze is

to be used as a heating medium. Propylene glycol
has a higher viscosity than water therefore the
system pressure drop will be higher.

10. Indirect Water Heater: An indirect water heater

should be piped in a dedicated zone. It consists of a
water tank that is heated by boiler water passing
through an internal coil. Examples of indirect water
heating are shown in the System Piping subsection
of this Section.

WATER PIPING AND CONTROLS

The circulator sizing given is for primary/secondary
installations only. The system circulators must be
sized based on the flow and pressure drop
requirements of the system.

NOTICE

Output

64,000

=

= 6.4 GPM

T x 500

20 x 500

Required Flow =

Table 3.3 – Flow Rate and Pressure Drop

Boiler

Model

Flow Rate

(GPM [LPM])

Pressure Drop

(Feet [meters])

PI-T50

4.0 (15.1)

4.5 (1.22)

PI-T80

6.4 (24.2)

5.0 (1.52)

PI-80

6.4 (24.2)

5.0 (1.52)

PI-140

11.2 (42.4)

8.0 (2.44)

PI-199

15.9 (60.2)

13.0 (4.02)

Table 3.4 – Recommended Circulators

Boiler

Model

TACO

Circulator

Grundfos Circulator

PI-T50

006

UPS 15-58FC SPD-1

PI-T80

007

UPS 15-58FC SPD-2

PI-80

007

UPS 15-58FC SPD-2

PI-140

0010

UPS 15-58FC SPD-3

PI-199

0011

UP 26-64F