34

Fault

Code

Description

Corrective Action

F00

High Limit Exceeded.

1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu

and confirming that there is less than a 50°F rise from the return thermistor to the

supply thermistor.

3. If gray thermostat wires are being used, disconnect them and jump them together.

If F00 code can be reset check thermostat circuit for short circuit or stray voltage.

4. Check supply temperature reading on LED display. Replace High Limit Switch if

supply temperature is below 210°F.

5. Temporarily jump out Water Pressure Switch. If F00 code can be reset check wiring

harness and connections. If wiring harness is okay replace Water Pressure Switch.

F01

Vent Temperature Limit Exceeded.

1. Push the red reset button on the switch.
2. Check the flue temperature during operation using a combustion analyzer.
3. Replace the switch if faulty.

F02

Interrupted or Shorted

Supply (Outlet) Thermistor.

1. Check the electrical connection to the thermistor on the outlet manifold.
2. Replace thermistor if necessary.

F03

Interrupted or Shorted

Return (Inlet) Thermistor.

1. Check the electrical connection to the thermistor on the inlet manifold.
2. Replace thermistor if necessary.

F05

Supply (Outlet)

Temperature exceeded 230°F.

1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu

and confirming that there is less than a 50°F rise from the return thermistor to the

supply thermistor.

F06

Return (Inlet) Temperature

exceeded 230°F.

1. Check circulation pump operation.
2. Assure that there is adequate flow through the boiler by accessing the status menu

and confirming that there is less than a 50°F rise from the return thermistor to the

supply thermistor.

F09

No flame detected – The boiler will make three

attempts at ignition before the control goes into

this lockout condition.

1. Watch the igniter through the observation window provided.
2. If there is no spark, check the spark electrode for the proper ¼" gap.
3. Remove any corrosion from the spark electrode.
4. If there is a spark but no flame, check the gas supply to the boiler.
5. If there is a flame, check the flame sensor.

F10

Loss of Flame Signal – The boiler will relight 4

times before the control goes into this lockout

condition.

1. Check the gas pressure to the gas valve while the unit is in operation.
2. Assure that the flame is stable when lit.
3. Check to see if the green light on the display module is out while the boiler

is running.

4. If the green light doesn't come on or goes off during operation check the flame

signal on the status menu.

5. If the signal reads less than 1 microampere, clean the flame sensor.
6. If the sensor continues to read low, replace it.

F11

False Flame Signal – The boiler will lock out if

it senses a flame signal when there should be

none present.

1. Turn the gas off to the unit at the service valve.
2. If the flame signal is still present replace the flame rod.
3. If the flame signal is not present after turning off the gas supply, check

the gas valve electrical connection.

4. If there is no power to the gas valve, remove the valve and check for obstruction

in the valve seat or replace the gas valve.

5. Turn the gas on at the service valve after corrective action is taken.

F13

Combustion Fan Speed Low – The boiler will

lock out if it senses that the fan speed is less than

70% of expected for more than 60 seconds.

1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.

F14

Combustion Fan Speed High – The boiler will

lock out if the fan speed is more than 130% of

expected for more than 60 seconds.

1. Check the combustion air fan wiring.
2. Replace the combustion air fan.
3. Replace the control board.

F18

Gas Valve Error

1. Make sure the connector is correctly connected to the gas valve.
2. Check the electrical wiring from the valve to the control board.
3. Replace the gas valve.
4. Replace control board.

F30

Watchdog

Call factory for further assistance.

F31

Parameter Memory

Call factory for further assistance.

F32

Parameter Memory Write Error

Call factory for further assistance.

F33

Programming Error

Call factory for further assistance.

NC

Neutral Fault – Boiler locks out if it senses

a voltage drop or power feedback on the

neutral wire.

1. Check for adequate supply voltage.
2. Check for power feedback on the neutral wire.

Table 8.2: P125 Control Board Fault Codes

TROUBLESHOOTING