Ionizer problem detection control, Ionizer operation case study – Panasonic CS-E21CKE User Manual

Page 31

Advertising
background image

3. Ionizer operation status is not memorised by micon. After OFF, when operation is “ON” again, air conditioner operates

without ionizer operation.

c. Timer during ionizer operation

Refer to case study in next page for detail.

8.1.18.1. Ionizer Problem Detection Control

i. Purpose

To inform user of ionizer problems and detection.

ii. Two types of problem detection control:

Control

Detection Method

Protection

Recovery

ERROR
PROTECTION

(i) Actual ion: ON

(i) Actual ion ON for 10s & OFF for

30 min. continuously for 24 times
(approx. 11 hr. 30 min.)

(i) Actual ion is permanently OFF & ion

LED is blinking.

(i) Press ON/OFF button

to OFF

(ii) ion feedback signal:

0V

(ii) Within 24 counts, if anytime

CONDITION becomes false then
count is cleared.

(ii) Press remote control ion button for

a) ON: Ion LED blink & buzzer = beep
b) OFF: Ion LED OFF & buzzer = beep

(ii)

(iii)

Reset power

Off by force operation

BREAKDOWN
PROTECTION

(i)

(ii)

Actual ion: OFF

ion feedback signal:
5V

(i) Actual ion OFF

2s

(i)

Case 1: During Air-Con. ON.
Air-Cond OFF with abnormal no. H26 is
activated with timer LED is blinking
permanently.

(i) When anytime

CONDITION becomes
false.

(i)

Case 2: During Air-Con. OFF.
Abnormal no. H26 is activated with
timer LED is blinking permanently for
both cases 1 & 2.

(ii) Once recovered, ion &

Timer LED stops
blinking permanently.

(ii) Press remote control ion button for

a) ON: Ion LED blink
b) OFF: Ion LED OFF

(iii) Main power reset.

(iii) Press any remote control button to

a) ON: Buzzer = beep beep beep beep
b) OFF: Buzzer = beep beep beep beep

8.1.18.2. Ionizer Operation case study

Case 1

31