5. Charging hose

• The pressure resistance of the charging hose has been

raised to match the higher pressure of R410A. The hose
material has also been changed to suit HFC use, and
the size of the fitting has been changed to match the
manifold ports.

6. Vacuum pump adaptor

• When using a vacuum pump for R410A, it is necessary

to install an electromagnetic valve to prevent the
vacuum pump oil from flowing back into the charging
hose. The vacuum pump adaptor is installed for that
purpose. if the vacuum pump oil (mineral oil) becomes
mixed with R410A, it will damage the unit.

7. Electric gas leak detector for HFC refrigerant

• The leak detector and halide torch that were used with

CFC and HCFC cannot be used with R410A (because
there is no chlorine in the refrigerant).

• The present R134a leak detector can be used, but the

detection sensitivity will be lower (setting the sensitivity
for R134a at 1, the level for R410A will drop to 0.6).

• For detecting small amounts of gas leakage, use the

electric gas leak detector for HFC refrigerant. (Detection
sensitivity with R410A is about 23 g/year).

Fig. 4 Manifold gauge charging hose

Fig. 5 Vacuum pump adaptor

Fig. 6 Electric gas leak detector for HFC refrigerant

Table 8 Difference between R410A and conventional charging hoses

Conventional hoses

R410A hoses

Pressure
resistance

Working pressure

3.4 MPa (35 kgf/cm

3

)

5.1 MPa (52 kgf/cm

3

)

Bursting pressure

17.2 MPa (175 kgf/cm

3

)

27.4 MPa (280 kgf/cm

3

)

Material

NBR rubber

HNBR rubber Nylon coating inside