8.2.1.7. CT Disconnection Detection

1. Control Starting Condition

a. Total Current is below 0.74 ~ 0.94 Amp.

b. Operating Frequency is 72 Hz (E18CK), 95 Hz (E21CK) +1 and above.

c.

Continuously for 20s.

2. Control Contents

a. Abnormal signal transmitted to indoor unit after 3 minutes outdoor power is supplied. (Indoor unit stop)

3. Control Cancellation Condition

Starting condition, (1) is not fulfilled.

8.2.1.8. Low Frequency Protection Control 1

When the compressor operate at frequency lower than 22 Hz for 240 minutes, the operation frequency will be increased to 22 Hz
for two minutes.

8.2.1.9. Low Frequency Protection Control 2

When all the below conditions occur, minimum value (Freq. MIN) for the frequency instructed to compressor will change to 30 Hz.

Temperature, T, for:

Cooling/Soft Dry

Heating

Indoor intake air (°C)

T

15 or T

30

T

14 or T

28

Outdoor air (°C)

T

13 or T

38

T

4 or T

24

Indoor heat exchanger (°C)

T

30

T

0

8.2.1.10. Minimum Frequency Protection Control

• During cooling operation (Anti Freezing control, soft dry) carry out the following operation.

1. During remote control setting is less than 28 deg

Indoor Fan Speed

Above Hi

minHz =

21

Above Me-

minHz =

21

Less than Me-

minHz =

18

Auto

minHz =

16

2. During Powerful ON

minHz =

22

However, when less than thermo OFF for 120 sec. continuously, the above control will be cancel.

• During heating operation, operate the followings control.

1. During Remote Control setting is less than 18 deg

Indoor Fan Speed

Above Hi

minHz =

30

Above Lo

minHz =

25

Less than Lo

minHz =

15

2. During Powerful ON

minHz =

35

However, when less than thermo OFF for 100 sec. continuously, the above control will be cancel.