3-3 Electrical Connections


CAUTION: before connecting the appliance, make sure that the supply
power line is disconnected from the network.

General Power Supply Characteristics

• Neutral mode TT and TN.S; the circuit of the heat pump must be

connected to the earth circuit


Connections

• The electric installation must be carried out by a qualified professional or

electrician

• The power supply of the heat pump must come from an independent

circuit and have the appropriate circuit protection.

• The controller must be installed on an indoor wall in an easily accessible

area.


Electrical Protection

• Circuit breaker curves D or standard fuse protection Am, gauged with

16A

• Differential protection of 30mA


Connection to an Electrical Plug

• The heat pump comes packaged with an electric cable and plug.

• The plug must be safe, protected from rain and water and the condition

checked regularly

Before starting the heat pump hot water cylinder, it is important to fully read this
manual and understand the operation and the settings.