Premier Heat Pumps – Water Heater and Chiller Manual

Page 16

5 - Instructions for the Installer


The installer must read the following and provide instructions to the purchaser.

5-1 Unit controller and parameters


The Heat Pump is Equipped with

2 Control Devices:

• A defrost temperature probe, located on the evaporator, starts the defrost

sequence.

• A thermal probe located on the exchanger ensures the cut of the heat

pump when the temperature of the water reaches the temperature
required.

• The meaning of the code name


T1:

water temperature

T2:

ambient temperature

T3:

exhaust temperature from compressor

T4:

coil temperature in outdoor heat exchanger

TC:

water temperature setting



Control Function:

1) TC can be set between 10C-35°C in cooling mode. Original TC is 18°C.

When T1≤T°C -1°C, Compressor and fan motor stop; When T1≥T°C
+1°C, Compressor and fan motor start.

2) TC can be set between 45°C -60°C in heating mode. Original TC is

50°C. When T1≤TC-1C, Compressor and fan motor start; When
T1≥TC+1C, Compressor and fan motor stop. When compressor is
running, if T2≤12°C, the four way valve2 on; if T2≥12°C, the four way
valve2 off.

5-2 Defrost operation:

1) Defrost:

The system begins to defrost if the following three terms are met in the
same time:

a) T4≤-5°C lasts for a while;
b) compressor runs continuously for more than 5 minutes
c) Compressor runs accumulative total for 45 minutes

While the system begins to defrost, compressor and fan motor stop first and
four way valve1 is on after 1 minute and begins to work. The compressor
restarts after it has stopped for 3 minutes. If the sensor for T4 is damaged, the
system begins to defrost, after the compressor has run continuously for 45