4.1 Commissioning of an External Battery Cabinet

The following table shows the designations of the battery cabinets which are available for the UPS devices.

Table 2. External Battery Packs

Model

Cabinet

Batteries

Active 700

NA

NA

Active 1000

BPActive1000-19

2x (3 x 7. 2 Ah)

Active 2000

BPActive3000-19

2x (8 x 7. 2 Ah)

Active 3000

BPActive3000-19

2x (8 x 7. 2 Ah)

Disconnect the UPS from the mains and the loads from the UPS.

CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.

CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.

Connect the battery cabinet types BP1000, BP3000 to the UPS using the supplied cable. The connection
scheme is shown in the figures below. Switch the circuit breaker on the battery cabinet to the ON position.

The UPS is now ready for operation.

NOTE: Battery charging times may be longer when using an external battery cabinet.

WARNING:

Battery Plug 1

Circuit Breaker

Battery Plug 2

Fig. 13: Connection of Battery Extensions for devices Active 1000

WARNING: The connection of the external battery cabinet may only be done by qualified personnel
in accordance with the applicable safety regulations.

CAUTION: For the electrical installation, the maximum load capacity of the connection cable has to be taken into
account.