Rackmount Solutions VA 10000 User Manual

Page 55

Advertising
background image

Chloride Active and E-Series UPS User Manual

51

Interference immunity

IEC 801-2,level 4 / IEC 801-3,level 3
IEC 801-4,level 4 / IEC 801-5,level 2

Efficiency

> 86%

>90%

>85%

Cooling

Fan

Common Data (continued)

Noise level mains operation

< 50 dBa

< 55 dBa

<65 dBa

Noise level battery operation

< 55 dBa

<65 dBa

<65 dBa

Operating temperature

+ 50°F to +105°F (+10°C to + 40°C)

recommended +59°F to +89°F (+15°C to + 32°C)

Storage temperature

+5°F to +104°F (-15°C to +40°C)

Relative humidity

20% to 90%, non-condensing

Altitude

max. 10,000 ft. (3,000m),

above 5,000 ft. (1,500m) max ambient temperature = 95°F

(35 °C)

Mechanical Data

UPS

Weight - lbs.

347

580

787

Dimensions - HxWxD in. (mm)

27.8 x 10.6 x 22.5

(705 x 270 x 570)

38 x 13.4 x 25

(965 x 340 x 670)

46.5 x 16.5 x 31.5

(1180 x 420 x

800)

Battery extension

Type

BPE61

BPE101

Weight lbs

337

894

Dimensions - HxWxD in. (mm)

27.8 x 10.6 x 22.5

(705 x 270 x 570)

38 x 15 x 26.4

(965 x 380 x 670)

Signals

Visual

LED-indication at the front side

Audible

Acoustical alarm

Communications

RS232 interface

Alarm contacts +5V...+12V

Signal input +5V...+12V

ethernet

Table 12. Chloride E-Series UPS North America

UPS Model

E61XA

(E41XA*)

E101XA

(E81*)

E203XA

(E153XA*)

Advertising