Chloride Active and E-Series UPS User Manual

Fig. 28: Connection of an External Battery Cabinet to Type E101

Fig. 29: Connection of an External Battery cabinet to Type E203

WARNING: The connection of the external battery cabinet may only be done by qualified personnel
in accordance with the applicable safety regulations.

CAUTION: For the electrical installation, the maximum load capacity of the connection cable has to be taken into
account.

Table 9. Technical data of the connection cable

E101

E203

Minimum permissible cable cross section

6 mm

2

, 8 AWG

4 AWG

Maximum permissible cable cross section

20 mm

2

, 4 AWG

4 AWG

Nominal operating voltage

240 VDC

240 VDC