Rackmount Solutions VA 10000 User Manual

Page 6

Advertising
background image

2

Chloride Active and E-Series UPS User Manual

• Transport the unit only in suitable packaging (protect against jolts and shocks).
• If the equipment is moved indoors from a cold environment, condensation may occur. Before you place

the equipment in service it must be absolutely dry. An acclimatization period of at least two hours is
required.

• This equipment must be installed in an indoor, temperature controlled environment that is free of

conductive contaminants. See chapter 10, “Active Tower and Rackmount Specifications” on page 22
for specific environmental limits.

• The Active equipment has a safety-tested power cable and may only be connected to a properly

grounded receptacle.

• The switch

(see chapter 2, “Display and Operation Elements (Active)” on page 3) does not isolate

the device (UPS) from the mains. To isolate completely from the mains, the main switch must be
switched off and the power plug disconnected.

CAUTION: Removing mains power may not remove power from the device (UPS) output. See instructions above to
properly remove power from output.

• In case of interruption of the mains voltage, the integrated battery maintains the power supply to the

connected equipment.

• Lay all cables so that nobody can stand on them or trip over them. When connecting the device to the

power supply, follow the instructions in the chapter on “Active Installation and Commissioning” on
page 11.

• No data transmission lines should be connected or disconnected during a thunderstorm.
• Make sure that no objects (e.g. pins, necklaces, paper clips, etc.) get inside the device.
• In emergencies (e.g. damaged case, controls or power cables, penetration of liquids or foreign matter)

put the device into BYPASS, disconnect the power plug and contact Chloride Technical Services at

1-800-879-5011.

• Do not connect equipment that will overload the UPS (e.g. laser printers or vacuum cleaners) or

demand DC-current (e.g. half-wave rectifiers or hair dryers).

• When cleaning the unit, follow the instructions in chapter 7, “Maintenance (Active)” on page 19.
• The sum of the leakage currents (protective conductor current) of the UPS and the connected devices

must not exceed 3.5 mA for the types Active 700, 1000, 2000 and 3000.

Chloride Active UPS is UL listed under UL1778 for North American units.

Advertising
This manual is related to the following products: