Rackmount Solutions VA 10000 User Manual

Page 27

Advertising
background image

Chloride Active and E-Series UPS User Manual

23

Efficiency

> 83%

Protection class

IP 20

Cooling

Fan

Noise level mains operation

< 41 dBa

< 41 dBa

< 50 dBa

< 50 dBa

Noise level battery operation

< 45 dBa

<45 dBa

< 50 dBa

<50 dBa

Operating temperature (ambient)

+ 50°F to +105°F (10°C to + 40°C)

recommended +59°F to +89°F (+15°C to + 32°C)

Storage temperature

+5°F to +104°F (-15°C to +40°C)

Relative humidity

20% to 90%,non-condensation

Altitude

max. 10,000 ft. (3000m),

above 5,000 ft. (1500m) max ambient temperature = 95°F

(35 °C)

Mechanical Data

UPS

Weight - lbs. (kg)

28.6 (13)

35.3 (16)

75 (34)

75 (34)

Dimensions - HxWxD in. (mm)

8.9 x 5.7 x 16 (225 x 145 x

405)

13.8 x 7.9 x 18.5 (350 x 200

x 470)

Battery extension

Type

None

BPActive

1000

BPActive

3000

BPActive

3000

Weight lbs (kg)

None

42 (19)

106 (48)

106 (48)

Dimensions - HxWxD in. (mm)

None

8.9 x 5.7 x

16

(225x145x4

05)

13.8 x 7.9 x 18.5

(350 x 200 x 470)

Signals

Visual

LED-indication at the front side

Audible

Acoustical alarm

Communications

RS232 interface

Alarm contacts +5V...+12 V

Signal input +5V...+12 V

Ethernet (optional)

Table 5. Chloride Active UPS North America

UPS Model

Active 700

Active 1000

Active 2000

Active 3000

Advertising
This manual is related to the following products: