Installation, Horizontal vent terminal location, Figure 9 – Rheem Commercial Power Direct Vent Water heater User Manual

Page 11: Canadian installations, Us installations

Advertising
background image

11

installation

3. Maximum twenty-four (24) inches above roof level without

additional support for vent pipe.

4. Four (4) feet from any gable, dormer or other roof structure with

building interior access (i.e., vent, window, etc.).

5. Ten (10) feet from any forced air inlet to the building. Any

fresh or make-up air inlet such as a dryer or furnace area is

considered to be a forced air inlet.

6. The inlet is a minimum of six (6) inches vertically above the outlet.

7. Terminals are a minimum of seven (7) inches horizontally apart with

a maximum of twenty-four (24) inches.

VENT INSTALLATION – Before proceeding, make certain you

understand the procedure and cautions covered in the section

“Joining Pipes and Fittings.”

VERTICAL VENT INSTALLATION – Once the vent termi-

nal location has been determined, make a hole through the

roof and interior ceiling to accommodate the vent pipe. Com-

plete the vent pipe installation to the water heater’s vent

connector fitting on the blower outlet. Support vertical or

horizontal runs as previously mentioned.

Install adequate flashing where the vent pipe passes through the

roof. Determine the vent terminal height and cut vent pipe ac-

cordingly. Refer to Fig. 8 for proper vent terminal height. Connect

vent elbow onto vertical pipe through roof. Connect short piece

of vent pipe (approximately 3" long) to elbow, then join terminal

to the short piece of vent pipe.

VERTICAL VENT TERMINAL LOCATION – The location of

vertical vent terminal depends on the following considerations

(see Figure 8):

1. Minimum twelve (12) inches above roof.

2. Minimum twelve (12) inches above anticipated snow level.

D

V

V

E

FIXE

D

CLO

SED

OPE

RAB

LE

OPE

RAB

LE

FIXE

D

CLOS

ED

v

v

B

L

F

C

B

v

v

v

X

B

B

B

A

J

C

I

H

X

v

M

K

v

G

A

The following information should be used for determining the proper location of the vent terminal

for direct vent water heaters.

V VENT TERMINAL

X AIR SUPPLY INLET

AREA WHERE TERMINAL IS NOT PERMITTED

Horizontal Vent Terminal Location

Canadian Installations

1

US Installations

2

A= Clearance above grade, veranda,

porch, deck or balcony.

12 inches (30 cm) above anticipated

snow level.

12 inches (30 cm) above anticipated

snow level.

B= Clearance to window or door that may

be opened.

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 12 inches (30 cm) for appli-

ances > 10,000 Btuh (3kW) and < 100,000

Btuh (30kW), 36 inches (91 cm) for appli-

ances > 100,000 Btuh (30kW).

6 inches (15 cm) for appliances < 10,000

Btuh (3 kW), 9 inches (23 cm) for appli-

ances > 10,000 Btuh (3 kW) and

< 50,000 Btuh (15 kW), 12 inches

(30 cm) for appliances > 50,000 Btuh

(15 kW).

C= Clearance to permanently closed

window.

*

*

D= Vertical Clearance to ventilated soffit

located above the terminal within a

horizontal distance of 2 feet (61 cm)

from the center line of the terminal.

3 feet (91 cm)

3 feet (91 cm)

E= Clearance to unventilated soffit.

*

*

F= Clearance to outside corner.

*

*

G= Clearance to inside corner.

18 inches (46 cm)

18 inches (46 cm)

Figure 9 -

Horizontal Vent Terminal Location