System sentinel” troubleshooting guide – Rheem Commercial Power Direct Vent Water heater User Manual

Page 22

Advertising
background image

22

YES

CAUTION

!

label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERiFY PROP-

ER OPERATiON AFTER SERViCiNg!

Section 3... the “igNiTiON” lED

“System Sentinel” Troubleshooting guide

is the Blower Operating?

1. Remove ignition Cable and check for

good continuity, replace if necessary.

2. Check ignitor Electrode(s) gap for proper

spacing (1/8” to 5/32”). Correct if neces-

sary.

3. Examine Ceramic insulator on Pilot

Assembly for cracks. Replace if cracks

are evident.

if all of the above components check okay,

replace ignition Control module.

is 24 VAC present between the

gray ground wire and the Red

24 V wire connected to the igni-

tion Control module?

is there 24 VAC present

between the common and

Normally open terminal of

pressure switch 1?

is Spark ignitor operating?

(Can sparking be heard?)

The System Sentinel Panel is

defective and must be replaced.

Wiring harness is defec-

tive and must be replaced.

Check Con-

tinuity of the

Red wire from

the ignition

module to

the Pressure

Switch.

is continuity

good?

The Thermostat has called for

heat, the Blower is running, and

24 VAC power is being supplied to

the ignition Control module and

the ignition sequence will begin.

YES

YES

YES

YES

NO

NO

NO

NO

NO

is the ignition lED illuminated?

is there 120 VAC

across Black wire

and White wire of

blower?

YES

NO

is there 120

VAC between

the black wire at

the relay and the

white wire on the

transformer?

NO

YES

Blower is

d e f e c t i v e

and must be

replaced.

Check continuity

of black wire from

relay to blower

motor and white

wire to motor.

is continuity

good?

Check continuity

of black wire to

relay.

is continuity

good?

YES

C h e c k

wire con-

nections.

NO

W i r e

is defec-

tive and

must be

replaced.

is there 120 VAC between the

black wire on the relay (power

going to blower) and the white

wire of the transformer?

is 24

VAC present

across coil

of relay?

YES

R e l a y i s

d e f e c t i v e

and must be

replaced.

NO

YES

Review pressure switch circuit

on this page.

Recheck all connections,

should have power at blower motor.

YES

NO

Check con-

t i nu i t y o f

yellow wires

to pressure

s w i t c h e s

and between

switches.

is continuity

good?

Pressure Switch

is defective and

must be replaced.

P o w e r

should be

at 24 VAC

of ignition

module.

NO

YES

YES

NO