Unconfined space, Confined space, Vent adapter – Reliance Water Heaters D85500PE User Manual

Page 15: Venting installation, Venting, Unconfined space confined space vent adapter

Advertising
background image

15

through the water heater’s vent system causing poor combustion.

Sooting, serious damage to the water heater and the risk of fire

or explosion may result. It can also create a risk of asphyxiation.
louVers and grilles

The free areas of the fresh air openings in the instructions that

follow do not take in to account the presence of louvers, grilles

or screens in the openings.
The required size of openings for combustion, ventilation

and dilution air shall be based on the “net free area” of each

opening. Where the free area through a design of louver or

grille or screen is known, it shall be used in calculating the

size of opening required to provide the free area specified.

Where the louver and grille design and free area are not

known, it shall be assumed that wood louvers will have 25%

free area and metal louvers and grilles will have 75% free

area. Non motorized louvers and grilles shall be fixed in the

open position.

Vent adapter

The D85500Ne/D85500Pe model is shipped with a 6" to 8"

diameter vent adapter (Fig. 11). The vent adapter fits on top of

the installed blower exhaust. Use only vent adapters supplied

with the unit. The venting must comply with the NATIONAL

FUeL GAS CODe, ANSI Z223.1/NFPA 54 and for Canadian

installations consult the Canadian Installation Code CAN/CSA

B149.1-00.

figure 11

Never obstruct the flow of ventilation air. If you have any doubts

or questions at all, call your gas supplier. Failure to provide the

proper amount of combustion air can result in a fire or explosion

and cause property damage, serious bodily injury or death.

unconfined space

An Unconfined Space is one whose volume IS NOT LeSS ThAN

50 cubic feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the

total input rating of all appliances installed in the space. rooms

communicating directly with the space, in which the appliances

are installed, through openings not furnished with doors, are

considered a part of the unconfined space.
makeup air requirements for the operation of exhaust fans,

kitchen ventilation systems, clothes dryers and fireplaces shall

also be considered in determining the adequacy of a space to

provide combustion, ventilation and dilution air.
unusually tight construction

In unconfined spaces in buildings, infiltration may be adequate

to provide air for combustion, ventilation and dilution of flue

gases. however, in buildings of unusually tight construction (for

example, weather stripping, heavily insulated, caulked, vapor

barrier, etc.) additional air must be provided using the methods

described in the Confined Space section that follows.

confined space

A Confined Space is one whose volume IS LeSS ThAN 50 cubic

feet per 1,000 Btu/hr (4.8 cubic meters per kW) of the total input

rating of all appliances installed in the space.
Openings must be installed to provide fresh air for combustion,

ventilation and dilution in confined spaces. The required size for

the openings is dependent on the method used to provide fresh

air to the confined space AND the total Btu/hr input rating of all

appliances installed in the space.
exhaust fans

Where exhaust fans are installed, additional air shall be provided

to replace the exhausted air. When an exhaust fan is installed

in the same space with a water heater, sufficient openings to

provide fresh air must be provided that accommodate the

requirements for all appliances in the room and the exhaust fan.

Undersized openings will cause air to be drawn into the room

Venting installation

Venting

The INSTrUCTIONS IN ThIS SeCTION ON VeNTING mUST

Be FOLLOWeD TO AVOID ChOkeD COmBUSTION Or

reCIrCULATION OF FLUe GASeS. SUCh CONDITIONS

CAUSe SOOTING Or rISkS OF FIre AND ASPhyXIATION.
heater must be protected from freezing downdrafts.
remove all soot or other obstructions from the chimney that will

retard a free draft.
Type B venting is recommended with these heaters. For

typical venting application see TeChNICAL DATA VeNTING

on page 18.
This water heater must be vented in compliance with all local

codes, the current revision of the National Fuel Gas Code

(ANSI-Z223.1) and with the Category I Venting Tables.
If any part of the vent system is exposed to ambient temperatures

below 40°F it must be insulated to prevent condensation.

• Do not connect the heater to a common vent or chimney

with solid fuel burning equipment. This practice is

prohibited by many local building codes as is the

practice of venting gas fired equipment to the duct work

of ventilation systems.

figure 12

• Where a separate vent connection is not available and the

vent pipe from the heater must be connected to a common

Advertising
This manual is related to the following products: