vent with an oil burning furnace, the vent pipe should enter

the smaller common vent or chimney at a point above the

large vent pipe.

multiple heater manifold

Figure 13 and Table 7 should be used for horizontally manifolding

two or more heaters.

figure 13

fresh air openings for confined spaces

The following instructions shall be used to calculate the size,

number and placement of openings providing fresh air for

combustion, ventilation and dilution in confined spaces. The

illustrations shown in this section of the manual are a reference

for the openings that provide fresh air into confined spaces

only. DO NOT refer to these illustrations for the purpose of vent

installation. See Venting Installation on page 15 for complete

venting installation instructions.

outdoor air through two openings

figure 14

The confined space shall be provided with two permanent

openings, one commencing within 12 inches (300 mm) of the top

and one commencing within 12 inches (300 mm) of the bottom of

the enclosure. The openings shall communicate directly with the

outdoors. See Figure 14.
each opening shall have a minimum free area of 1 square inch

per 4,000 Btu/hr (550 mm2 per kW) of the aggregate input rating

of all appliances installed in the enclosure. each opening shall

not be less than 100 square inches (645 cm2).

outdoor air through one opening

figure 15

Alternatively a single permanent opening, commencing within 12

inches (300 mm) of the top of the enclosure, shall be provided. See

Figure 15. The water heater shall have clearances of at least 1 inch

(25 mm) from the sides and back and 6 inches (l50 mm) from the

front of the appliance. The opening shall directly communicate with

the outdoors or shall communicate through a vertical or horizontal

duct to the outdoors or spaces that freely communicate with the

outdoors and shall have a minimum free area of the following:
1. 1 square inch per 3000 Btu/hr (733 mm

2

per kW) of the total

input rating of all appliances located in the enclosure, and

2. Not less than the sum of the areas of all vent connectors in

the space.

outdoor air through two horiZontal ducts

figure 16

The confined space shall be provided with two permanent

horizontal ducts, one commencing within 12 inches (300 mm) of

the top and one commencing within 12 inches (300 mm) of the

bottom of the enclosure. The horizontal ducts shall communicate

directly with the outdoors. See Figure 16.
each duct opening shall have a minimum free area of 1 square

inch per 2,000 Btu/hr (1100 mm

2

per kW) of the aggregate input

rating of all appliances installed in the enclosure.
When ducts are used, they shall be of the same cross sectional

area as the free area of the openings to which they connect.

The minimum dimension of rectangular air ducts shall be not less

than 3 inches.